E-80-136KTL User Manual
Copyright ©EVOLVE ENERGY GROUP CO.,LTD
- 59 -
side
)
ID23
HwADFaultIdcBra
nch
Current Branch
sampling faulty
ID24
HwADFaultIdc
DC input current
sampling faulty
ID29
ConsistentFault_G
FCI
The GFCI sampling
value between the
master DSP and
salve DSP is not
consistent
ID17-ID24 are internal faults of
inverter, turn OFF the
“
DC
switch
”
, wait for 5 minutes, then
turn ON the
“
DC switch
”
.
Check whether the fault is
rectified. If no, please contact
technical support.
ID30
ConsistentFault_V
grid
The Grid voltage
sampling value
between the
master and salve
is not consistent
ID31
ConsistentFault_D
CI
ID33
SpiCommFault(DC
)
SPI Communication
Faulty
(
DC
side
)
ID34
SpiCommFault(AC
)
SPI Communication
Faulty
(
AC side
)
ID35
SChip_Fault
Chip Faulty
(
DC
side
)
ID36
MChip_Fault
Chip Faulty
(
AC
side
))
ID41
RelayFail
Relay faulty
ID42
IsoFault
Low isolation faulty
ID43
PEConnectFault
Ground faulty
ID44
PvConfigError
Input mode
incorrect