E-80-136KTL User Manual
Copyright ©EVOLVE ENERGY GROUP CO.,LTD
- 36 -
Figure 5-7 AC Terminal size
5.4.4 Wring Procedure
The section will use a five-core wire as a sample, four core wire has same
connection process
Figure 5-1 Recommend AC cable size
Name
Type
Area(mm
²
)
AC Cables
Recommended
:
Outdoor
four-core/five-core copper or
aluminum wire
Copper Wire: 95~185; Aluminum
Wire: 120~240;
PE Wire: reference 5.3
STEP 1
:
Open the cover, refers to section 5.3.1
STEP 2
:
Turn OFF the AC circuit breaker and secure against reconnection