21
3.7
Pressure Independent Control Valve (PICV) Adjustment
MANUAL ADJUSTMENT OF THE QMAX (MAXIMUM PRIMARY FLOW)
FOR THE CORRECT USE
OF THIS PRODUCT,
WATER QUALITY MUST
BE HIGH AND COMPLY
WITH CURRENT BSRIA & CIBSE
GUIDELINES AND EVINOX
REQUIREMENTS.
Please note that the flow rates stated
are subject to a + / - 10% tolerance.
TECHNICAL
DATA
91L
¾”
91H ¾”
93L
1”
ModuSat
TP
HEATING
40/50/60
‐
10
ModuSat
TP
40/50
‐
10
DHW
ModuSat
TP
60
‐
10
DHW
Max
flow
rate
1000 l/h
0.278 l/s
1500 l/h
0.417 l/s
2200 l/h –
0.611 l/s
Max.
Flow
accuracy
[
∆
p
0.3
÷
1
bar]
±10%
±10%
±10%
Start
‐
up
∆
p
→
Q=const.
25 kPa
0.25 bar
35 kPa
0.35 bar
25 kPa –
0.25 bar
Max
∆
p
400 kPa – 4 bar
400 kPa – 4 bar
400 kPa – 4 bar
Temperature
-10 ÷ 120 °C
-10 ÷ 120 °C
-10 ÷ 120 °C
Max
working
pressure
2500 kPa
25 bar
2500 kPa
25 bar
2500 kPa
25 bar
Connections
Rp 3/4” F
EN10226-1
Rp 3/4” F
EN10226-1
Rc - EN10226-1
91L ¾”
91H ¾”
93L 1”
ModuSat
TP
HEATING
40/50/60
‐
10
ModuSat
TP
40/50
‐
10
DHW
ModuSat
TP
60
‐
10
DHW
PRE-
SETTING
%
Flow
l/h
Flow
l/s
Flow
l/h
Flow
l/s
Flow
l/h
Flow
l/s
100% 1000
0,278
1500
0.417
2200 0.611
90%
900
0,250
1350 0,375
1980
0.550
80% 800
0,222
1200
0,333
1760 0.489
70%
700
0,194
1050 0,292
1540
0.428
60% 600
0,167
900
0,250
1320 0.367
50%
500
0,139
750
0,208
1100
0.306
40% 400
0,111
600
0,167
880 0.244
30%
300
0,083
450
0.125
660
0.183
20% 200
0,056
- -
440
0.122
10%
100
0,028
-
-
220
0.061
Flow
Carefully Lift up locking
device
Select the flow rate by rotating the
pre-setting ring
Carefully Push down
locking device
The PICV contained within the
ModuSat is a combined flow
regulation, DP control and energy
valve. The valve will be pre-set
during commissioning based on the
design parameters, however
adjustment can be to the Qmax
(Maximum flow) if required.
*
*