BIONIBAL corrosion inhibitor is approved by Evinox and is a requirement in installations
that incorporate our boiler plant. Thorough research shows that Bionibal protects your
installation in 4 key ways:
FIRST LEVEL
- corrosion inhibition and prevention of rust build up.
SECOND LEVEL -
acidic component that stops bacteria and algae growth, particularly
useful in under floor heating working at low temperatures.
THIRD LEVEL -
prevents the adherence of suspended particles such as tartar, keeping
the surfaces clean (pumps, valves, heat meters, etc.).
FOURTH LEVEL -
provides traceability to enable the dosage to be fully monitored and
guarantee the best protection level. It also provides a trace element to enable any
leaks to be quickly identified.
Electrolytic corrosion prevention
, in a circuit employing different metals.
IT IS ADVISABLE
to
ADD
a suitable approved corrosion inhibitor
before the
system is put in operation.
Bionibal dosage and use (If used & when required if Evinox boiler plant is installed)
NEW INSTALLATIONS:
Fill the circuit with water and check for leaks
.
Empty the circuit in order to discard
any installation residuals (if necessary clean it with an appropriate product and
make sure that the circuit is well rinsed).
Once the circuit is well cleaned, fill it with water again and add
BIONIBAL
according to the dosage indicated.
EXISTING INSTALLATIONS:
Because
BIONIBAL
doesn’t dissolve existing limes and other residuals
accumulated over the years, proceed with empting the circuit and perform a
thorough cleaning process of it. Use accredited companies for this work.
Once the circuit is well cleaned, fill it with water again and add
BIONIBAL
according to the dosage indicated below:
IMPORTANT WARNING
Bionibal must only be put in a thoroughly clean installation that has been fully checked. It
is therefore imperative to fill the entire system one or more times with clean water and
flush / drain as required. In some cases, the system may need washing by a suitable
product:
SUGGESTED DOSE
2 litres for every 100 litres of primary network
1 litre for every 100 litres of the radiator circuit capacity
2 litres for every 100 litres of the under floor heating circuit capacity with oxygen
blocking barrier pipes
The system cannot be overdosed with Bionibal and will not cause system damage.
Restore the correct concentration every time the circuit is emptied / topped up
with raw untreated water.