39
6.3
Use of the commissioning switch
The commissioning switch is located inside the case of the ModuSat next to the
manometer and heat meter display. This switch enables the unit to be put into a manual
heating ‘on’ mode prior to full unit commissioning to enable the testing of the secondary /
apartment heating circuit. Please note that this function should not be used until the
secondary installation is complete i.e. flushed, treated and refilled to the correct pressures.
To enable the heating run mode setting the button should be depressed and held in for
approximately 30 seconds. The heating PICV opens and the pump starts its self venting
procedure (As described in section 6.5). The unit will then run at a pre-set output
temperature of 45°C thus providing a safe temperature for UFH circuits and also a gentle
warm up of radiator circuits. This function will run for a pre-set period of approx.
45minutes.
If the heating needs to be run again, the process is repeated and then the cycle will start
and run for a further 45 mins.
Please note: The rocker switch above the commissioning push button is the Pump
Manual Override. This should NOT be operated or used by persons other than
Evinox Engineers as it is for emergency use only.
Commissioning
Switch
Pump Manual
Override Rocker
Switch