Every 3 months - Replace the per-filter cartridge:

 

1.  Close the inlet shut-off valve. 
2.  Open  the  TO  flush  valve  to  relieve  the  pressure.  Observe  that  the  pressure  gauge 

reads zero. 

3.  Place  a  bucket  under  the  sump  to  catch  any  excess  water  that  may  spill  from  the 

head.  Un-screw  the  sump  with  the  wrench  provided.  Remove  the  old  cartridge  and 
clean the sump if required.  

4.  Install the new cartridge and re-install the sump.  
5.  Slowly open the inlet shut-off valve and purge the system of any air.  
6.  Close the TO flush valve. 

 

Every 6 months – Replace the TO cartridge:

 

1.  Close the inlet shut-off valve. 
2.  Disconnect the 24 VAC Transformer from the 115-Volt receptacle. 
3.  Open  the  TO  flush  valve  to  relieve  the  pressure.  Observe  that  the  pressure  gauge 

reads zero. 

4.  Follow the instructions on the TO cartridge label. Place a bucket under the cartridge 

to catch any excess water that may spill from the head. Remove the old cartridge by 
turning  the  cartridge  to  the  left  until  it  stops  and  pulling  it  downward  until  it  is  free 
from its head. 

5.  Remove the shrink-wrap plastic from the new TO cartridge. 
6.  Align the new pre-filter cartridge lug with its head label. 
7.  Holding the head and cartridge firmly, press the cartridge upward onto the head and 

turn the cartridge to the right until it stops. 

8.  Slowly open the inlet shut-off valve and purge the system of any air.  
9.  Allow the TO cartridge to flush to drain for 5 minutes or until the water is clear. 
10. Close the TO flush valve. 
11. Connect the 24 VAC Transformer from the 115-Volt receptacle. 

 

Every 6-12 months – Sanitize the storage tank:

 

1.  Refer to “Start-up” section - steps 1-3, for sanitation procedure. 
 

Every 1 to 1-1/2 years – Replace the RO cartridge: 

1.  Close the inlet shut-off valve. 
2.  Disconnect the 24 VAC transformer from the 115-Volt receptacle. 
3.  Open  the  TO  flush  valve  to  relieve  the  pressure.  Observe  that  the  pressure  gauge 

reads zero. 

4.  Follow the instructions on the RO cartridge label. Place a bucket under the cartridge 

to catch any excess water that may spill from the head. Remove the old cartridge by 
turning  the  cartridge  to  the  left  until  it  stops  and  pulling  it  downward  until  it  is  free 
from its head. 

5.  Remove the shrink-wrap plastic from the new RO cartridge. 
6.  Align the new RO cartridge lug with its head label. 
7.  Holding the head and cartridge firmly, press the cartridge upward onto the head and 

turn the cartridge to the right until it stops. 

8.  Rotate the handle on the product water 3-way sample valve so it is pointing towards 

the drain connection (front of unit). 

9.  Slowly open the inlet shut-off valve. 
10. Connect the 24 VAC transformer to the 115-Volt receptacle. 
11. Demand  water  from  one  of  the  pieces  of  equipment  serviced  by  the  MRS-200  to 

drain  down  the  storage  to  the  point  the  solenoid  energizes  and  the  system  begins 
make RO water. Stop demanding water once this occurs. 

12. Allow  the  system  to  flush  at  least  1  hour  or  until  1  gallon  of  outlet  water  has  been 

produced.  Check  the  water quality  to  determine  if the  RO  membrane  is  functioning 
correctly. 

Содержание MRS-200

Страница 1: ...1 Cat No EV311117 Rev B 11 6 03 DCO 7060 MODEL MRS 200 Reverse Osmosis Mineral Reduction System Installation and Start up Guide...

Страница 2: ...Installation 4 Cartridge Installation and Activation 10 Start Up and Blend Adjustment 10 Adjusting the Recovery 12 Operation 14 Maintenance 14 Performance Monitoring 16 TDS Measurement 16 Performance...

Страница 3: ...hlorine An activated carbon filter has been provided with this system to protect the reverse osmosis membrane from chlorine attack Influent chlorine should not exceed 3 mg L The MRS 200 System consist...

Страница 4: ...nd permit access for maintenance The system will weigh approximately 175 pounds when the storage tank is full 4 ____ Does the inlet water supply meet the requirements listed below 1 A minimum of 1 0 G...

Страница 5: ...nts Place the main unit on the shelf positioning the cartridge heads directly over the cutout area Insert a cable tie into one of the holes in the baseplate and through the wire slats in the shelf mak...

Страница 6: ...A MP S 2 INS E RT E LB OW FULLY 3 S LIDE LOCK ING CLIP UP TO S E CURE 1 S LIDE LOCK ING CLIP DOW N Figure 3 4 Water supplies with a dynamic operating pressure of 50 PSI or less require the use of the...

Страница 7: ...UMP 10 NUT 8 1 2 X 1 SPACER 4 10 X 1 1 2 SCREW 8 10 WASHER 16 MOUNTING PLATE Figure 4 5 Refer to Figure 5 for a sample general arrangement Use this as a guideline for determining valve location tubing...

Страница 8: ...ow control insert red plastic cylinder in small parts kit Press this insert into the red OD tubing Fig 6 Attach the end of the tubing with the flow control insert into the 3 8 stem x OD tube reducing...

Страница 9: ...lt receptacle at this time Figure 9 Figure 7 Figure 8 INLET WATER SUPPLY 50 PSIG MAX TO 120 VAC OUTLET A B C SOLENOID VALVE 1 5 2 4 3 IN A B C TO 120 VAC OUTLET SOLENOID VALVE IN COVER REMOVED 3 4 2 5...

Страница 10: ...ative solution from the RO cartridge and should not be consumed 6 If you are utilizing the capillary tubing assembly refer to the section titled Adjusting the Recovery for instructions Return to this...

Страница 11: ...to contain a range of TDS greater than what an RO system normally produces In those cases a filtered water blend valve has been provided to blend in filtered not RO treated water to attain a specific...

Страница 12: ...product flow with a 1000 ml graduated cylinder Don t worry if the flow is slightly more or less than what is specified 2 Determine the appropriate concentrate flow for your system and the desired rec...

Страница 13: ...480 70 520 80 554 10 00 50 408 60 450 70 489 80 521 12 00 50 363 60 402 70 437 80 467 14 00 50 330 60 366 70 399 80 427 16 00 50 307 60 342 70 371 80 397 18 00 50 292 60 326 70 352 80 377 20 00 50 28...

Страница 14: ...or 6 000 12 000 18 000 or 24 000 gallons d Calendar scale is jumper selectable for 6 months or 12 months Monitor operation a Active green light blinks every two seconds during any minimum water flow c...

Страница 15: ...s or until the water is clear 10 Close the TO flush valve 11 Connect the 24 VAC Transformer from the 115 Volt receptacle Every 6 12 months Sanitize the storage tank 1 Refer to Start up section steps 1...

Страница 16: ...and a graduated cylinder or calibrated measuring cup The drain water flow rate can be measured from the end of the red tubing in a similar manner Inlet water flow Outlet Product Water Flow Drain Wate...

Страница 17: ...has removed 92 of the dissolved solids from the inlet water 6 The RO cartridge should be changed every 1 to 1 1 2 years or when the percent reduction falls below 90 A form has been provided below to r...

Страница 18: ...valve as required to attain specified water quality a Tubing piping run to equipment too restrictive a Increase tubing piping diameter Refer to System Installation section for recommendations 4 Low w...

Страница 19: ...19 Replacement Parts...

Страница 20: ...EV307850 Support Ring EA 2 49 EV310445 Label Carbon Filter EA 1 50 EV310446 Label RO Module EA 1 51 01010248 Adaptor 3 8 Stem X 1 4 Tube EA 1 53 EV306996 Directional Arrow EA 1 No Part Number Descrip...

Страница 21: ...hole punched Prints black ink on 50 offset white VENDOR MUST SUBMIT A MATERIAL CERTIFICATE OF COMPLIANCE WITH EACH SHIPMENT LET CHANGE BY APRVD DATE A DCO 4785 RH SK 9 12 02 B DCO 7060 KR RH 11 6 03 T...

Отзывы: