8.3 

ALARM MENU

To enter ALARM menu and see the active alarms, press the enter key from the scrolling menu. 
Then press the right arrow key to get past METER  and then press ENTER once the ALARM 
menu is visible. Once in the ALARM menu you may see an active alarm present if the heads up 
LED lamp is illuminated. If no alarms are active, the display will read NO FAULTS. The following 
alarms are available through the diagnostics within the Lite-Minder inverter.

Start Up Faults:

BACKFEED 

This indicates that there is AC already at the output terminals

 

 

Most likely scenario is that the Lite-Minder was wired incorrectly

ROTATION

 

This indicates that there is a wiring fault on the transformer

 

 

Most likely scenario is that if a PCB was replaced, there was a mis-

 

 

wire when re-connecting the transformer. 

 

 

                  

 

                                                                           

OVERLOAD

 

This indicates that there is too much output or a short circuit load

 

 

connected.  

 

 

MIS WIRE

 

This indicates there is lack of AC power at the input

BATT LOW

 

This indicates that the Batter Voltage is too low to start the unit up

 

 

Possible fault is that the battery is mis-wired, fuse is open or batteries are

 

 

dead

Faults While Lite-Minder is on Battery Charging:

AC FUSE

  

Indicates a blown fuse on the input AC. Fuse location is on the PCB

CHARGER

 

Indicates that the charger has malfunctioned

OVERLOAD

 

Indicates that there is too much load connected

OVERTEMP

 

Indicates that the FET’s Heatsink temperature has exceeded its limits

Faults While Lite-Minder is on Battery Power:

LOW VOUT

 

Indicates that the inverter could not produce enough voltage to

 

 

support the load

FET O C

   

Indicates that there was a severe overload that caused the crest factor

 

 

to  be exceeded too many times and the inverter shut down to protect itself

 

 

from failure

LVD 

 

The inverter ran on battery until the Low Voltage Disconnect point

OVERLOAD 

There is too much load connected to the output

OVERTEMP

 

Indicates that the FET’s Heatsink temperature has exceeded its limits

Pg. 17

Содержание Lite-Minder

Страница 1: ...g by unauthorized personnel E The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition F Do not use this equipment for other than intended use This unit contain...

Страница 2: ...on 5 2 Battery Installation 5 3 DC Voltage of System 6 0 Start up and Shut down procedures 6 1 Start up Procedure 6 2 Shut down Procedure 7 0 Specifications 8 0 User Interface 8 1 Scrolling Display 8...

Страница 3: ...ation PWM and the latest MOSFET technology Lite Minder can produce a Pure Sine wave output which is compatible with all types of lighting loads A high crest factor of 4 is extremely beneficial for hig...

Страница 4: ...bient temperatures no warmer than 77 F 25 C For storage temperatures greater than 77 F 25 C the batteries must be recharged one 1 month sooner for every 5 F 3 C increase above 77 F 25 C Storage Temper...

Страница 5: ...ntly depreciate battery life Heat is the determining factor of battery life Every means should be made to keep the batteries in an environment that keeps the batteries around 25 degrees C for rated ba...

Страница 6: ...the Gear Tray forward and lift up while supporting from below disconnect AC Input Output connectors and Installation Switch cable remove 4 screws remove the AC Breaker Terminal Block Assembly Gear Tra...

Страница 7: ...1 4 20 bolts No unit dis assembly is required Enclosure Outline Inverter hooks on to plate and is secured by 2x 1 4 20 bolts in battery compartment Plate is fastened to wall or struts hardware suppli...

Страница 8: ...tablished At NO time is drilling allowed into the cabinet Drilling causes metal filings to be deposited on surfaces and could land on the Printed Circuit Boards and cause short circuits WARNING Drilli...

Страница 9: ...ersonal protective equipment PPE that is suitable such as eye protection when working near batteries 4 1 Removing the Top Cover All the connections for the AC input and output are located on the top r...

Страница 10: ...iver NOTE AC Input and AC output wires must be run in separate conduit or raceways per NEC ARTICLE 700 Please ensure all codes and standards are observed NOTE Lite Minder requires that the Neutral and...

Страница 11: ...INPUT CONNECTIONS GROUND BAR POWER PCB CONNECTIONS OPTIONAL SUMMARY ALARM CONNECTIONS WIRE PORTS Note Up to three output circuit breakers can be mounted on the terminal block rail Standard AC Input Ou...

Страница 12: ...y mounted and secured in a permanent location with all conduit and AC wiring connected 5 1 Battery Inspection Inspect the batteries for any physical damage such as cracks or any other sign of leaking...

Страница 13: ...afe manor to accomplish the system buss requirements NOTE Battery potential has galvanic isolation from AC potential Any battery voltage measurements must be made with both meter leads connected to th...

Страница 14: ...ess the Test button on the front panel to verify that the normally off and switched output loads are all operational and again measure currents If alarms occur during start up see section 8 3 for poss...

Страница 15: ...THD Crest Factor 4 for 525W model 6 5 for 325W model Load Power Factor 0 5 lead to 0 5 lag Protection Optional circuit breakers Output Types Normally On Normally Off and Switched Output Battery Type V...

Страница 16: ...ht arrow in the scrolling display mode will advance or retard the scroll Pressing Escape in any of the Sub Menu s will retard back one menu level Pressing Escape multiple times will always return the...

Страница 17: ...connected MIS WIRE This indicates there is lack of AC power at the input BATT LOW This indicates that the Batter Voltage is too low to start the unit up Possible fault is that the battery is mis wire...

Страница 18: ...ndicate how deep the battery was discharged and if it correlates to a healthy battery The largest benefit of the log though is to keep record of tests and events for Safety Inspectors so they can see...

Страница 19: ...up to the maximum output current capability of the Lite Minder To change this value press ENTER at this menu and then there will be a display capable of scrolling with the right arrow key that will r...

Страница 20: ...ed by tickling the output to a low voltage for one cycle and looking for overcurrent faults This diagnostic features connects all the outputs such as the Normally Off and the Switched Output MISWIRE T...

Страница 21: ...Power mode the inverter is producing a pure sine wave for the output loads and the batteries are being discharged The output current is limited by an active pulse by pulse current limit technique and...

Страница 22: ...Warranty Duration Pure Lead 7 years full 13 years pro rata High Rate 3 years full 7 years pro rata Standard VRLA 1 year full 9 years pro rata Extended Warranty is available through a factory start up...

Страница 23: ...of the logs will see how the unit is performing A quick test by manually pressing the test button will transfer the system to Battery Power and will turn on all the connected loads such as the Normall...

Страница 24: ...urrent available just not nearly as much By running the battery to LVD the available fault current would be substantially less and safer if an inadvertent short circuit were to happen during the remov...

Отзывы: