11.0  Maintenance and Service 

CAUTION – Whenever maintenance and service is to be performed, it may be 
desirable to shut unit down. Please refer to Start up and Shut Down procedures for 
details.
CAUTION – Always assume AC and DC Voltages are present at the Lite-Minder 
terminals because the inverter is capable of providing output voltage from the 
batteries when there is no AC input. The unit can pass through AC voltages from input 
to output with no batteries connected if the installation switch is on.

Routine Maintenance

Routine Maintenance should be considered any maintenance that does not require removing 
the Inverters’ shroud (top/front cover). These maintenance items includes Circuit breaker re-
setting and periodic cleaning of dust from the cover and cabinet base to ensure proper 
convection air flow. Since no fans are required on this system, air flow moves by convection. 
Convection air circulation is from bottom to top as heat naturally rises. 
Keep all foreign objects off the top and away from the sides of the unit as these may impede 
convection air flow.
Lite-Minder automatically performs monthly tests (every 28 days) and keeps a log of all the 
events and monthly tests in the event log. Lite-Minder has a self-clearing 28 day counter and 
resets any time the unit transferred to battery power. If on day 14 the unit had a brief power 
outage, the counter gets reset and 28 days later (pending no other transfers) a monthly test 
would be performed.
Periodic inspection of the logs will see how the unit is performing. A quick test by manually 
pressing the test button will transfer the system to Battery Power and will turn on all the 
connected loads such as the Normally Off and the Switched Output load.
Ensure there are no faults present. If there are faults, please refer to the User Interface section 
for a complete detail of what this fault may indicate.

Test

By pressing the TEST button on the front panel, the unit will transfer to Battery Power. This test 
will run for at least 15 seconds and will exit back to Battery Charging upon synchronizing to 
utility power.

Yearly Test

The NFPA code requires that a yearly test of 90 minutes be performed and the system must be 
able to run the full 90 minutes without going into a LVD fault.
A yearly test of 90 minutes can be initiated by holding in the TEST button for 5 seconds. When 
the system enters into the yearly test, the scrolling display will display90M TEST, MIN:XX, 
where XX is the elapsed minutes during the yearly tests. The elapsed time starts at 00 and 
ends at 90.
An alternate method of performing the 90 minute yearly test would be to turn off the input 
breaker for the 90 minutes and then re-apply when the 90 minute duration is complete. 

11.1  Battery Maintenance 

The batteries used in the Lite-Minder are sealed lead calcium and are termed “Maintenance 
Free”. This term may be misleading because ALL batteries require periodic maintenance even 
if it only consists of a visual inspection. We recommend the following maintenance plan:
* Once every 3 to 4 months the batteries should be visually inspected for cracks, leaks, 
bulging or deformities and corrosion buildup on terminals.

Pg. 23

Содержание Lite-Minder

Страница 1: ...g by unauthorized personnel E The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition F Do not use this equipment for other than intended use This unit contain...

Страница 2: ...on 5 2 Battery Installation 5 3 DC Voltage of System 6 0 Start up and Shut down procedures 6 1 Start up Procedure 6 2 Shut down Procedure 7 0 Specifications 8 0 User Interface 8 1 Scrolling Display 8...

Страница 3: ...ation PWM and the latest MOSFET technology Lite Minder can produce a Pure Sine wave output which is compatible with all types of lighting loads A high crest factor of 4 is extremely beneficial for hig...

Страница 4: ...bient temperatures no warmer than 77 F 25 C For storage temperatures greater than 77 F 25 C the batteries must be recharged one 1 month sooner for every 5 F 3 C increase above 77 F 25 C Storage Temper...

Страница 5: ...ntly depreciate battery life Heat is the determining factor of battery life Every means should be made to keep the batteries in an environment that keeps the batteries around 25 degrees C for rated ba...

Страница 6: ...the Gear Tray forward and lift up while supporting from below disconnect AC Input Output connectors and Installation Switch cable remove 4 screws remove the AC Breaker Terminal Block Assembly Gear Tra...

Страница 7: ...1 4 20 bolts No unit dis assembly is required Enclosure Outline Inverter hooks on to plate and is secured by 2x 1 4 20 bolts in battery compartment Plate is fastened to wall or struts hardware suppli...

Страница 8: ...tablished At NO time is drilling allowed into the cabinet Drilling causes metal filings to be deposited on surfaces and could land on the Printed Circuit Boards and cause short circuits WARNING Drilli...

Страница 9: ...ersonal protective equipment PPE that is suitable such as eye protection when working near batteries 4 1 Removing the Top Cover All the connections for the AC input and output are located on the top r...

Страница 10: ...iver NOTE AC Input and AC output wires must be run in separate conduit or raceways per NEC ARTICLE 700 Please ensure all codes and standards are observed NOTE Lite Minder requires that the Neutral and...

Страница 11: ...INPUT CONNECTIONS GROUND BAR POWER PCB CONNECTIONS OPTIONAL SUMMARY ALARM CONNECTIONS WIRE PORTS Note Up to three output circuit breakers can be mounted on the terminal block rail Standard AC Input Ou...

Страница 12: ...y mounted and secured in a permanent location with all conduit and AC wiring connected 5 1 Battery Inspection Inspect the batteries for any physical damage such as cracks or any other sign of leaking...

Страница 13: ...afe manor to accomplish the system buss requirements NOTE Battery potential has galvanic isolation from AC potential Any battery voltage measurements must be made with both meter leads connected to th...

Страница 14: ...ess the Test button on the front panel to verify that the normally off and switched output loads are all operational and again measure currents If alarms occur during start up see section 8 3 for poss...

Страница 15: ...THD Crest Factor 4 for 525W model 6 5 for 325W model Load Power Factor 0 5 lead to 0 5 lag Protection Optional circuit breakers Output Types Normally On Normally Off and Switched Output Battery Type V...

Страница 16: ...ht arrow in the scrolling display mode will advance or retard the scroll Pressing Escape in any of the Sub Menu s will retard back one menu level Pressing Escape multiple times will always return the...

Страница 17: ...connected MIS WIRE This indicates there is lack of AC power at the input BATT LOW This indicates that the Batter Voltage is too low to start the unit up Possible fault is that the battery is mis wire...

Страница 18: ...ndicate how deep the battery was discharged and if it correlates to a healthy battery The largest benefit of the log though is to keep record of tests and events for Safety Inspectors so they can see...

Страница 19: ...up to the maximum output current capability of the Lite Minder To change this value press ENTER at this menu and then there will be a display capable of scrolling with the right arrow key that will r...

Страница 20: ...ed by tickling the output to a low voltage for one cycle and looking for overcurrent faults This diagnostic features connects all the outputs such as the Normally Off and the Switched Output MISWIRE T...

Страница 21: ...Power mode the inverter is producing a pure sine wave for the output loads and the batteries are being discharged The output current is limited by an active pulse by pulse current limit technique and...

Страница 22: ...Warranty Duration Pure Lead 7 years full 13 years pro rata High Rate 3 years full 7 years pro rata Standard VRLA 1 year full 9 years pro rata Extended Warranty is available through a factory start up...

Страница 23: ...of the logs will see how the unit is performing A quick test by manually pressing the test button will transfer the system to Battery Power and will turn on all the connected loads such as the Normall...

Страница 24: ...urrent available just not nearly as much By running the battery to LVD the available fault current would be substantially less and safer if an inadvertent short circuit were to happen during the remov...

Отзывы: