Page 33/34
Make sure the ventilation air flow is correct and there is
not any obstruction at the ventilation inputs and output
grill.
With all circuit breakers down, check presence of
voltage at
the main terminal block:
Phase – Phase à~ 400 V
Phase – Neutral à~ 230 V
Phase – Earth à~ 230 V
Earth – Neutral à0 V
Validate the EARTH loop value (< 20 ohms condition
dry)
Earth value:
………………… Ohm
Check the equipotential connection between the metal
parts of the charger, including door, with the main
earthing terminal block
With all circuit breakers down, Switch ON circuit breaker
D3, with the door OPEN, verify that the LEDs are lit RED
that the display screen is ON.
Update software if needed.
Close the door and verify that the LEDs are lit RED and
that the screen displays “CHARGER UNAVAILABLE”
Open the door again and Switch ON circuit breaker D1
and close the door. Verify that the LED on the DC side
is GREEN. Verify that the LED on the AC side is RED.
Open the door again and Switch ON circuit breaker D7
and Check the RCD function by the test button,
reconnect it after
the test.
Close the door. Verify that the LED is GREEN on the AC
side.
Press the emergency button, one message will be
displayed saying that the charger is unavailable. To turn
the system on, simply turn and release the emergency
stop button by applying a small turn to the right.
Open the door again, Switch OFF circuit breaker D1
and D3, insert the SIM card in the screen, Switch ON
circuit breaker D3 and configure the connection to the
network controller if it is necessary. See User Manual.
Содержание Troniq
Страница 1: ...D000782AA6 EVBox Troniq Installation Manual ...
Страница 27: ...Page 27 34 8 APPENDIX 3 DIMENSIONS Charger dimensions without Auxiliary power cabinet APC ...
Страница 28: ...Page 28 34 Charger dimensions with Auxiliary power cabinet APC ...
Страница 29: ...Page 29 34 9 APPENDIX 4 CONNECTION TERMINALS DETAILS POWER AND COMMUNICATION ...