68X216802
22
8)
Press the ENTER key to confirm your selection.
9)
Press the ENTER key to return to Advanced Set-up mode, or return to Measurement mode by
pressing the
∆∆
and
∇
∇
keys simultaneously (escape).
7.7
Configuration (ConF) sub-function
This group of parameters lets you configure the controller to suit your requirements.
7.7.1
Entering the Configuration sub-function
1)
Enter Advanced Set-up mode. Push the ENTER key and scroll to Advanced Set-up security
code “22”. Push the ENTER key again.
2)
Press the
∆∆
or
∇
∇
keys to scroll until the upper display shows “ConF”.
7.7.2
Selecting the alarm time lag
This parameter group lets you select a period of time before the alarm activates when your set point has
been overshot. You can select from 0 to 1999 seconds.
1)
Follow directions in 7.9.1 to enter Configuration mode.
2)
Press the ENTER key. Scroll with the
∆∆
or
∇
∇
keys until the
upper display shows a numerical value (in seconds) and the lower
display shows “AL.d”.
3)
Press the
∆∆
or
∇
∇
keys to select how long of an alarm delay (0
to 1999 seconds) you want.
4)
Press the ENTER key to confirm your selection.
5)
Proceed to 7.9.3, or return to Measurement mode by pressing the
∆∆
and
∇
∇
keys simultaneously
(escape).
7.7.3
Selecting steady or pulse contact for the alarm relay
This parameter group lets you select whether the alarm contact will operate as a steady contact or a
fleeting (single pulse) contact. Pulse contact closing time is 250 millisecond.
30
30
AL.d
AL.d
HOLD SETUP
HOLD SETUP
COnf
COnf
HOLD SETUP
Stdy
Stdy
ALC
ALC
HOLD SETUP
00
ALd
ALd
HOLD SETUP
HOLD SETUP
no
no
dEF
dEF
0.0
0.0
L.Ad
L.Ad
HOLD SETUP