CHAPTER 3 - INSTALLATION PROCEDURE
584S FREQUENCY INVERTER
3-13
EMC Filters to Reduce Line Conducted Noise
An EMC supply filter may be used with each 584S/620 drive module to reduce the line conducted noise. The
recommended filters are listed in table 3.4 below.
Table 3.4 AC Supply Filter Part Numbers for Conformance with EN55011 Class B (suitable for both generic
environments)
Eurotherm
Product
Rating
Watt
Loss
Eurotherm Filter
Part Number
584S Type 4
0.75kW - 5.5kW (380V to 460V) &
0.75kW - 2.2kW (208V to 240V) constant torque
20W
CO388966U021
584S Type 4
7.5kW (380V to 460V) & 4kW (208V to 240V)
constant torque
35W
CO388966U035
584S Type 5
All
25W
CO388966U045
584S Type 6
All
75W
CO464053U095
584S Type 7
All
158W
CO464053U200
The recommended EMC filters for the type 4 and 5 584S/620 are to be mounted behind the drive module (underfloor
mounting) and share the same footprint. They are suitable as standard for cubicle mount applications, as shown in
figure 3-2. For wall mounting a purpose designed pressed steel conduit (Part No. BA388844) is supplied with the
gland box, for mounting between the filter body and gland box is shown in the mechanical mounting drawing figures
3-3.
Figure 3-2. Filter Cubicle Mounting Details (584S/620 types 4 & 5)
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - [email protected]
Содержание 584S
Страница 122: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Страница 173: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Страница 174: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Страница 175: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...