Chapter 2 - PRE-INSTALLATION PLANNING
2-16
584S Frequency Inverter
Table 2.5 - Control Board Terminal Descriptions (Continued)
Terminal
Number
Terminal Description
16
17
RELAY 2
RELAY 2. Relay Contacts
These terminals are the contacts of internal Relay '2' the function of which is
configurable from the MMI.
18
+24V.
24V supply for use with digital inputs. Max. load 200mA.
19
0V.
0V for digital inputs.
20
RUN. Digital Input
The digital input used to run and stop the drive.
+24V =
run
0V
=
stop
21
FRAMP. Digital Input (Configurable)
This digital input can be used to select an alternative ramp rate, an alternative
ramp down
down
down
down rate during stopping or a PID reset. Refer to chapter 4 "Reconfigure
inputs"
FRAMP.
+24V =
function selected
0V
=
function deselected
22
DIRECTION. Digital Input
This digital input can be used to control the direction of the motor.
+24V =
reverse
0V
=
forward
23
EXTERNAL TRIP. Digital Input
This digital input can be used to trip the drive. The motor will coast until the trip is
reset. If no external trip used, connect to terminal 18 (+24V).
+24V =
no trip
0V
=
trip
24
JOG. Digital Input (Configurable)
This digital input can be used to implement the jog function. The
JOG SPEED
is
set from the MMI. Refer to Table 2.6 for further optional uses of this terminal.
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - [email protected]
Содержание 584S
Страница 122: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Страница 173: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Страница 174: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Страница 175: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...