F7.41
Cooling fan control
0: Fan running only when running
1: Fan always running
0
☆
F7.42
Timing function selection
0: Invalid ; 1: Valid
0
★
F7.43
Timing run time selection
0: F7.44 setting
1: AI1
2: AI2
3: Panel potentiometer Analog input range
corresponds~F7.44
0
★
F7.44
Timing run time
0.0Min~6500.0Min
0.0Min
★
F7.45
Current running reaches the set time.
0.0Min~6500.0Min
0.0Min
★
F7.46
Awakens frequency
dormancy frequency(F7.48)to maximum frequency
(F0.19)
0.00Hz
☆
F7.47
Awakens delay time
0.0s~6500.0s
0.0s
☆
F7.48
Dormancy frequency
0.00Hz~awakens requency(F7.46)
0.00Hz
☆
F7.49
Dormancy delay time
0.0s~6500.0s
0.0s
☆
F7.50
AI1 input voltage protection lower limit
0.00V~F7.51
3.1V
☆
F7.51
AI1 input voltage protection upper limit
F7.50~10.00V
6.8V
☆
F7.52
Output phase loss protection factor
0~50%
15%
☆
F7.53
Output phase loss detection time multiple
0.0~50.0
1.2
☆
F7.54
Jog mode setting3
Bits:
0: Forward
1: Reverse
2: Determine the direction from the main termina
Ten bits:
0: Restore to the previous state after jogging
1: Stop running after jogging
Hundred bits:
0: Recover to the previous deceleration time
after jogging
1: Keep the deceleration time the same
after jogging
002
☆
5.1.10 F8 Group - Fault and protection
Code
Parameter name
Setting range
Factory
setting
Change
F8.00
Overcurrent stall gain
0~100
20
☆
F8.01
Overcurrent stall protection current
100%~200%
-
☆
F8.02
Motor overload protection selection
0: Invalid 1: Enable
1
☆
F8.03
Motor overload protection gain
0.20~10.00
1.00
☆
F8.04
Motor overload pre-alarm coefficient
50%~100%
80%
☆
F8.05
Over-voltage stall gain
0~100
0
☆
F8.06
Over-voltage stall protection voltage / energy
consumption brake voltage
120%~150%
130%
☆
F8.07
Input phase loss protection selection
Units digit:Input phase loss protection selection
0: Invalid 1: Enable
Tens digit:contactor actuation protection
0: Invalid 1: Enable
11
☆
F8.08
Output phase loss protection selection
0: Invalid
1: Enable
1
☆
F8.09
Short~ground protection
0: Invalid 1: Valid
1
☆
F8.10
Number of automatic fault reset
0~32767
0
☆
F8.11
Fault DO action selection during automatic
fault reset
0: OFF
1: ON
0
☆
F8.12
Automatic fault reset interval
0.1s~100.0s
1.0s
☆
F8.13
Over-speed detection value
0.0~50.0% (Maximum frequency)
20.0%
☆
F8.14
Over-speed detection time
0.0~60.0s
1.0s
☆
F8.15
Detection value for too large speed deviation
0.0~50.0% (Maximum frequency)
20.0%
☆
F8.16
Detection time for too large speed deviation
0.0~60.0s
5.0s
☆