V-3-3 parameter setting:
When the system requires the drive DA1 0-5V signal output, you need to set the parameters as follows:
No.
Code
Parameter name
Setting
range
F2.07
DA1output function selection
Running frequency
0
F2.16
DA1 zero bias coefficient
-100.0%~+100.0%
0%
F2.17
DA1 gain
-10.00~+10.00
0.50
Note: DA1 jumper cap on drive control board needs to be shorted to V terminal.
When the system requires DA2 to provide 4-20mA signal output, the following parameters need to be set:
No.
Code
Parameter name
Setting
range
F2.08
DA2 output function selection
Output current
2
F2.18
DA2 zero bias coefficient
-100.0%~+100.0%
20.0%
F2.19
DA2 gain
-10.00~+10.00
0.80
Note: The DA2 jumper cap on the control board of the inverter needs to be shorted to I terminal.
V-4 Terminal block control forward /reverse running jog
V-4-1 Electrical diagram:
Three phase input power supply
380V 50/60Hz
%
Circuit breaker
Motor
M
FWD point motion/STOP
REV point motion/STOP
Terminal control to control positive and reverse point movement
V-4-2 Connection:
Control terminal DI3 corresponds to jog command, control terminal DI4 corresponds to Jog command.
V-4-3 Parameter setting:
No.
Code
Parameter name
Setting
range
F0.11
Command source selection
Terminal block control (LED on)
1
F1.02
DI3 terminal function selection
Forward JOG(FJOG)
4
F1.03
DI4 terminal function selection
Reverse JOG(RJOG)
5