Run pausing
The inverter slows down and stops, but all operating parameters are memorized. Such as PLC
parameters, wobbulate frequency parameters, and PID parameters. This terminal signal disappears,
the inverter reverts to the previous state of running before parking.
11
External fault normally
open input
When the signal is sent to the inverter, the inverter reports fault Err.15, and performs troubleshooting
according to fault protection action (For details, please refer to the function code F8.17).
12
Multi-speed terminal 1
The setting of 16 stage speed or 16 kinds of other command can be achieved through the 16 states of
the four terminals. For details, see Table 1
13
Multi-speed terminal 2
14
Multi-speed terminal 3
15
Multi-speed terminal 4
16
Ac/deceleration time
selection terminal 1
The selection of 4 ac/deceleration times can be achieved through the 4 states of the two terminals. For
details, see Table 2
17
Ac/deceleration time
selection terminal 2
18
Frequency source
switching
Used to switch between different frequency sources.
According to frequency source selection function code (F0.07) settings, the terminal is used to switch
between two frequency sources.
19
UP/DOWN setting
(Terminal, keyboard)
When the frequency reference is the digital frequency, this terminal is used to clear the changed
frequency value by terminal UP/DOWN or keyboard UP/DOWN, so that the reference frequency can
recover to the set value of F0.01.
20
Run command switch
terminal 1
When the command source is set to the terminal control (F0.11 = 1), the terminal can be used to
switch between terminal control and keyboard control.
When the command source is set to the communication control (F0.11 = 2), the terminal can be used
to switch between communication control and keyboard control.
21
Ac/deceleration
prohibited
Ensure the inverter is free from external signals affect (Except for shutdown command), maintain current
output frequency.
22
PID pause
PID is temporarily disabled, the inverter maintains current output frequency, no longer performs PID
adjustment of frequency source.
23
PLC status reset
When PLC pauses and runs again, this terminal is used to reset the inverter to the initial state of simple
PLC.
24
Wobbulate pause
When the inverter outputs at center frequency. Wobbulate will pause
25
Counter input
Input terminal of the count pulse
26
Counter reset
Clear counter status
27
Length count input
Input terminal of the length count.
28
Length reset
Clear length
29
Torque control
prohibited
When the inverter torque control is prohibited, the inverter will enter speed control mode.
30
High-speed pulse
input (Only valid for
DI5 )
DI5 is used as pulse input terminal.
31
Reserve
Reserve
32
Immediately DC
braking
If the terminal is active, the inverter switches directly to DC braking status
33
External fault normally
closed input
When the signal of external fault normally closed input is inputted into the inverter, the inverter will
report fault Err.15 and shutdown.
34
Frequency change
enable
If the function is set to be valid, when the frequency changes, the inverter does not respond to
frequency changes until the terminal state is invalid.
35
PID action direction
as reverse
If the terminal is valid, PID action direction opposites to the direction set by E2.03
36
External parking
terminal 1
Under keyboard control mode, the terminal can be used to stop the inverter, same as STOP key on the
keyboard.
37
Control command
switch terminal 2
Used to switch between terminal control and communication control. If the command source is
selected as terminal control, the system will be switched to the communication control mode when the
terminal is active; vice versa.
38
PID integral pause
When the terminal is active, the PID integral adjustment function is paused, but the proportion and
differential adjustments of PID are still valid.