5.3.4. Set sensor full scale
The sensor full scale value is the pressure corresponding to 20 mA. If a
pressure sensor is used the value should be in [bar]. For sensor part number
53417 the value should be as default “0.400”
Enter menu
[TCM//PortX]
by scrolling with
or
.
At
PortX:
press
ENTER
.
Scroll to
SFS:
using
or
.
Press
ENTER
to get the cursor.
Type the
sensor full scale value
and press
ENTER
to acknowledge. When
the cursor disappears it is finished.
Press
EXIT
two times to leave Set-Up mode.
5.4. Fluid specification
5.4.1. Set fluid name
The fluid name set in the TSM makes it possible to show the fluid name in
the info box for the graphic representation of the analogue sensor. It should
be set to the same value as in the PC database.
Enter menu
[TCM//PortX]
by scrolling with
or
.
At
PortX:
press
ENTER
.
Scroll to
FN:
using
or
.
Press
ENTER
to get the cursor.
Type the
name of the fluid
and press
ENTER
to acknowledge. When the
cursor disappears it is finished.
Press
EXIT
two times to leave Set-Up mode
5.4.2. Set fluid part number
The fluid part number set in the TSM makes it possible to show the fluid
part number in the info box for the graphic representation of the analogue
sensor. It should be set to the same value as in the PC database.
Enter menu
[TCM//PortX]
by scrolling with
or
.
At
PortX:
press
ENTER
.
Scroll to
FP:
using
or
.
Press
ENTER
to get the cursor.
Type the
part number of the fluid
and press
ENTER
to acknowledge.
When the cursor disappears it is finished.
Press
EXIT
two times to leave Set-Up mode