LUBE-MASTER R10
8(21)
TCM: ‡
TCM MainMenu
PortX: ‡
TCM MainMenu
O:0.000 ‡
Zero adjust
O:-0.120_ ‡
Zero adjust
O:-0.120 ‡
Zero adjust
TCM: ‡
TCM MainMenu
PortX: ‡
TCM MainMenu
C:1.000 ‡
Calibration
C:1.000 ‡
Calibration
C:1.000 ‡
Calibration
TCM: ‡
TCM MainMenu
PortX: ‡
TCM MainMenu
T:6 ‡
Time constant
T:6 ‡
Time constant
T:6 ‡
Time constant
5.3. Analogue sensor settings
5.3.1. Set the input signal filter time constant
This time constant (
Tau
) is used to filter the sensor signal to create an
accurate tank level. “0” means no filter and a higher value gives slower
response but a more accurate value. The default value of “6” is in most cases
good. It means that for a step in the tank level the reading of the level is on
99,9 % after 30 seconds.
Enter menu
[TCM//PortX]
by scrolling with
or
.
At
PortX:
press
ENTER
.
Scroll to
T:
using
or
.
Press
ENTER
to get the cursor.
Type the
time constant
and press
ENTER
to acknowledge. When the
cursor disappears it is finished.
Press
EXIT
two times to leave Set-Up mode.
5.3.2. Adjusting the offset
Offset adjusting is used to obtain “0” volume when the tank is empty. If the
sensor 53417 is used a normal value is –0.080. The “-“ sign is typed on the
keypad by first pressing down arrow (yellow) two times followed by the “?”
mark.
If the tank is empty, put the sensor in the tank at the bottom. If there is fluid
in the tank hold the sensor outside the tank at bottom level. Adjust the offset
value until the tank level shows “0”.
Enter menu
[TCM//PortX]
by scrolling with
or
.
At
PortX:
press
ENTER
.
Scroll to
O:
using
or
.
Press
ENTER
to get the cursor.
Type the
offset value
and press
ENTER
to acknowledge. When the cursor
disappears it is finished.
Press
EXIT
two times to leave Set-Up mode.
5.3.3. Adjusting the calibration
The calibration factor should normally be set to “1.018” if all other values
are set properly. The intention with the calibration factor is to set the
amplification so that the analogue input of the port matches the sensors
output.
Enter menu
[TCM//PortX]
by scrolling with
or
.
At
PortX:
press
ENTER
.
Scroll to
C:
using
or
.
Press
ENTER
to get the cursor.
Type the
calibration value
and press
ENTER
to acknowledge. When the
cursor disappears it is finished.
Press
EXIT
two times to leave Set-Up mode