
Instruction Manual ZHK
96/129
V07-19.0
Spray humidifier
-
Fill pan and U-trap with fresh water and adjust float valve so that valve closes with a water level
2-3 cm below the overflow. Ensure in any case, bubble-free suck in.
-
Open the valves on the pump pressure side and suction side (where applicable) completely.
-
Check the tightness of all tube connections. Retighten the clamps using a torque wrench. Fix
the screw with a torque of 5….6,5 Nm.
-
Start the pump and re-check all tube connections for tightness. Repeat this check after 10
hours of operation.
-
When pump is running at nominal RPM, check the manometer on the pressure side. The water
pressure at the manometer should be 2.5….3.0 bar –
if necessary close pressure side valve
accordingly.
-
Check pump strainer, washer nozzles and tubes for proper fit.
-
Check humidifier strainer and clean it if necessary.
Evaporative humidifier
General indications:
-
Check the proper installation of the PVC fins and droplet eliminator. The arrow must point in
direction of airflow (
-
Fins made from cellulose material can have initially an odor that is normal and will soon disap-
pear
.
Circulation water operation
-
The blowdown quantity is to be setup manually at the tacosetter.
Recommended setting (thumb): Bleed off rate = evaporation rate
-
Ensure that the pump impeller is completely covered by water. The water level must be regu-
lated by the maximum and minimum level switch.
-
Furthermore, it must be ensured by the control, that the designated conductivity, see
will not be exceeded. If the limit is reached, the blowdown valve must be opened.
High pressure spray humidifier
If no commissioning of the high pressure spray humidifier is agreed with EUROCLIMA, the manu-
facturer of the component must be contacted directly.
Steam Humidifier
The indications of the manufacturer of the steam humidifier must be observed for the commission-
ing.
Figure 193:
Installation of honey comb and droplet separator packages
Содержание ZHK Series
Страница 1: ...ZHK INSTRUCTION MANUAL ...