The correct quantity of refrigerant can be checked at the operating refrigeration circuit. In both sight
glasses (note: sight glass on receiver according to circuit execution not always supplied) refrigerant
must be visible. The sight glass in liquid line must be filled completely.
Expansion valve:
-
Check superheating of expansion valve, which should amount about 5 to 10K. Check that the
temperature sensor is correctly fitted as well as the pressure compensation pipe.
-
If an electronic expansion valve is used, necessary values must be entered into the correspond-
ing controller (according to the instructions of the valve manufacturer). Instructions from the valve
manufacturer are supplied by EUROCLIMA.
High pressure safety switch:
The high pressure switch stops the compressor when the allowed equipment pressure is exceeded.
A functional check must be carried out during commissioning and must be performed during any
during each maintenance work.
Low pressure safety switch:
The low pressure switch stops the compressor when the equipment pressure falls below the allowed
low pressure limit. A functional check must be carried out during commissioning and must be per-
formed at each maintenance work.
Handling:
If the unit goes into high or low pressure mode, the problem must be acknowledged at the control
panel for the compressors to start again.
Electrical superheat controller
The electronic superheat controller has an internal battery, so that the valve closes securely even
during power failures. Without this feature, the valve remains open, resulting in liquid hammering in
the compressor at the restart. Liquid hammering can cause damage of the compressor.
Therefore, the annual replacement of the battery is recommended for safety rea-
sons.
9.11.3
Inspection
Inspection work may be carried out by the operator in trimestrial intervals.
All equipment:
-
Have a look for loose links, fasteners etc., tighten if necessary.
-
Pay attention to unusual noise.
-
Have a look for oil leakage on components and joints.
-
Have a look at corrosion around piping of the refrigeration circuit, if necessary spraying again
with acrylic varnish.
Air-cooled condenser, direct expansion evaporator:
Clean fin surface if necessary. Dirty fins reduce the transmission of heat which could result in unac-
ceptable condensing / evaporation temperatures. Be careful not to damage the fins. Clean with com-
pressed air or a vacuum cleaner.
Compressor:
Check oil sight glass in the crankcase (if mounted). Pay attention to unusual noise. To start the
compressor manually, it has to proceed as described in
chapter 8.2.2