Instruction Manual ZHK
V07-19.0
55/129
Incorrectly mounted filters can be sucked in by the fan and lead to considerable
damage.
5.4.1
Panel filter and / or bag filter laterally removable
At laterally removeable filters a pull-out mechanism is included in the scope of supply, see
A seal is stuck to the filter. This seal is necessary, to avoid filter-bypass-leakages. If it is not in-
cluded in the scope of supply of EUROCLIMA, it must be provided by the customer.
The seal must be attached on the front side,
-
between the filters,
-
between filter and door,
-
between filter and back side wall.
Figure 125:
Pulling out the filters
Figure 126:
Pull-out mechanism
5.4.2
Panel filter and / or bag filters in filter frame
Filters are supplied loose and have to be fixed by clips as follows:
1. Take the filter clips, which are included in the supply and are attached to brackets on the filter
frame (
2. Four filter clips have to be inserted in the respective brackets according to
3. Finally, the filter must be fixed by the clips in the filter frame (
Figure 127:
Delivery of the clips
Figure 128:
Insertion of the clips
Figure 129:
Fixed filter