canopy
|
EOZ installation guide
The max number of Ozone Modules connected to a single Control Panel is 99, with a maximum length of 500m.
However, it may be advantageous to have multiple Control Panels in larger facilities for local monitoring purposes.
To connect multiple EOZ and/or Ozone Modules together they must be connected sequentially (“daisy-chained”)
from the Control Panel to the nearest device, then to next and so on. However, please note that although the
physical cabling is “chained” from one device to the next, the data cables are connected in a parallel format. In
this way data communications between devices will remain active even if one of them is powered off,
malfunctioning, or unplugged and removed.
Thus, each A, B+ and C data wire leading in from devices of any EOZ in the chain should share the same terminal
screw in its respective connector.
NOTE!
The following section applies only when installing multiple EOZ or Ozone Modules. If
installing only one unit, please skip to section “Control Panel and I/O wiring”.
Control Panel
EOZ-2
EOZ-1 nr. 1
EOZ-1 nr. 2
3x0,25 mm
2
3x0,25 mm
2
3x0,25 mm
2
C
B+
A-
IN
OUT