ETI SNOW SWITCH LCD-8 Скачать руководство пользователя страница 8

8

PART NO. 

24861 

REV 

A.0

INSTALLATION AND OPERATION MANUAL  |  

TO SAVE THE NEW VALUE

After changing parameters, hold the magnet over the magnetic 

switch for 3 seconds. The green LED turns off then flashes a 

brief message (3 short pulses and a long pulse), and return to 

normal mode. This can be done even if the parameters have 

not been changed.

TO ABANDON THE PROCESS WITH NO CHANGES

Allow the LCD-8 to sit for two (2) minutes. The unit will flash the 

green LED quickly for 2 seconds and return to normal 

operation, displaying a steady green LED. This can be done at 

any time in the process.

NOTE: changes to the operating temperature or the state of 

the low- temperature lockout take effect immediately. 

Changing the hold-on time does not affect any active hold-on 

cycles; new values will be used the next time a hold-on cycle 

initiates.

POST–INSTALLATION LCD-8 TEST

Most problems result from installation errors. Before testing, 

verify that unit is prop- erly installed.

Connect power to snow melting system. Wait 15 seconds; 

system should not actuate.

Using ice water or other cooling agent, cool ambient air 

temperature sensor to below 38°F (3.3oC); system should 

not actuate. Apply moisture to moisture sensing grid. 

System should actuate in less than 15 seconds.

Dry moisture sensing grid. Disconnect power to snow 

melting system. Wait 1 minute, then reconnect power. If 

system actuates, ensure sensing grid is dry and ambient air 

temperature is above 38°F (3.3°C), then repeat this step.

1.

2.

3.

TO ENTER THE CONFIGURATION PROCESS

The unit will flash the values of the three Field parameters in 

order, repeatedly. The pattern begins with:

The four (4) second gap helps the user identify Field 1, the 

starting point of the sequence, even after the sequences of 

pulses have repeated several times. The LCD-8’s default 

configuration is represented in Figure 6, above.

After changing the parameters of any field, the LCD-8 returns 

to the display mode.

Hold the magnet to the switch for 3 seconds

The green LED will go off

Remove the magnet

Process begins

TO CHANGE A FIELD’S PARAMETERS

Hold the magnet to the switch during the pause after that field. 

The green LED turns and remains on until the magnet is 

removed. That sets the value to 1. Positioning the magnet on 

again, the LED turns on, then remove the magnet: that sets that 

value to 2. Continue in this fashion.

There are two (2) seconds between swipes. After 2 seconds, the 

LCD-8 main- tains the entered value and returns to display 

mode.  If  a  value  exceeds  parameters,  the  green  LED  flickers 

briefly and returns to displaying the previous values.

Note: if the magnet is held for 3 seconds during the process of 

setting a value (having been released at least once), the green 

LED flickers briefly and restarts the display process.

Field 1’s green LED pulses

2 seconds between Field 1 and Field 2

Field 2’s green LED pulses

2 seconds between Field 2 and Field 3

Field 3’s LED pulses

4 seconds between Field 3 and returning to Field 1;

Содержание SNOW SWITCH LCD-8

Страница 1: ...ngle point of disconnect Size the circuit breaker in accordance with the size of the expected load The maximum current load for the LCD 8 is 3 amp resistive for 24 VAC Electrical Shock Fire Hazard CON...

Страница 2: ...enclosure Verifying system functionality after installation or when troubleshooting used to require spray circuit cooler or ice for controller activation The Sno TestTM feature eliminates this need b...

Страница 3: ...that it may be correctly processed upon receipt at Environmental Technology For more information about replacement parts or for a replacement Data Sheet or Manual please visit http www networketi com...

Страница 4: ...s off and the cup heaters energize for ten seconds Finally both are off for another ten seconds During this time the green LED blinks slowly one 1 second on one 1 second off Normal operation follows W...

Страница 5: ...ve 17 F but it enters the Lockout state instead if the temperature is below 17 F Additionally this Lockout state is entered if the temperature falls below 17 F during an automatic hold on cycle If the...

Страница 6: ...across this switch Figure 6 to start a hold on cycle or to terminate a running hold on cycle The magnetic switch determines whether the user s action swipes or holds the magnet during LCD 8 con gurat...

Страница 7: ...t is simply too cold to make operation practical The factory default low temperature lock out setting is Off meaning that the unit will try to activate the heaters regard less of ambient temperature S...

Страница 8: ...ensure sensing grid is dry and ambient air temperature is above 38 F 3 3 C then repeat this step 1 2 3 TO ENTER THE CONFIGURATION PROCESS The unit will ash the values of the three Field parameters in...

Страница 9: ...imer 0 1 3 default or 5 hours con gured by magnetic reed switch Set point temperature Off moisture only 36 F 38 F default 38 F con gured by magnetic reed switch INTERFACE Status indicators SUPPLY gree...

Страница 10: ...ressed or implied with respect to the contents of this publication or the products that it describes and speci cally disclaims any implied warranties of merchantability or tness for any particular pur...