LCD-8 24VAC OVERVIEW

general

PART NO. 

24861 

REV 

A.0

INSTALLATION AND OPERATION MANUAL  |  

The  Snow  Switch®  Model  LCD–8  (Figure  1)  is  a  configurable 

aerial snow melting system controller which makes automatic 

snow melting a cost-effective alterna- tive in even the smallest 

applications. Heaters operate at temperatures below the 

LCD-8’s configurable set point, 38°F (3.3°C) default, only when 

required. The adjust- able hold-on period, 3 hours default, 

continues heater operation after snow stops to ensure complete 

melting. The LCD–8 controller includes an internal magnetic 

reed switch used for manual heater cycling and configuring the 

controller’s operational temperature set point and hold-on time.

The LCD–8 controller is a model which operates from 24VAC 

with the configu- rable hold-on time and temperature set point.

It controls heater loads up to 3 amps resistive or 3 amps 

inductive. The operating temperature range extends from –40°F 

to  140°F  (–40°C  to  60°C).  The  redesigned,  patent  pending, 

rugged polycarbonate enclosure provides excellent protection 

at temperature extremes, while allowing snow to shed to 

prevent iglooing over the moisture sensor.

The internal magnetic reed switch allows for both configuration 

and manual heater operation without the need for external 

switches—which are susceptible to damage—or the need to open 

the enclosure.

Verifying system functionality after installation or when 

troubleshooting used to require spray circuit cooler or ice for 

controller activation. The Sno-TestTM feature eliminates this 

need by performing a self-test after power application and 

operating heaters in a unique pattern for a few seconds. 

Reading the test results takes only an AC voltmeter or clamp-on 

ammeter.

A configurable snow sensor with two light-emitting diode (LED) 

indicator lamps (Figure 2), the LCD-8 features a hold-on timer 

which allows its system to operate to a drier surface after 

melting snow.

The hold-on timer can be configured for off, 1 hour, 3 hours 

or 5 hours.  The operating temperature can be configured 

for none (precipitation sensor), 36°F, 38°F or 40°F.

The low-temperature lockout (17°F), which disengages unit 

operation, can be enabled or not.

Default configuration: 38°F operating temperature; 3 hour 

hold-on; no lockout. The LCD-8 uses an internal magnetic 

switch. The user swipes a magnet externally across this 

switch to start a hold-on cycle or to terminate a running 

hold-on cycle.  This switch may also be used to reconfigure 

the unit, or to view the current configuration.

The green LED, ordinarily on steady, blinks to indicate a 

concern with the unit. This LED is also used in the LCD-8’s 

configuration process.

The yellow LED indicator is lit whenever the output relay is 

powered (“on”). 

There  is  an  initialization  period  where  the  heaters  are 

tested.

FIGURE 1

LCD-8 24VAC

Green LED

Ambient Air

Temperature

Sensor

Yellow LED

FIGURE 2

LCD-8 LED LIGHTS

Содержание SNOW SWITCH LCD-8

Страница 1: ...ngle point of disconnect Size the circuit breaker in accordance with the size of the expected load The maximum current load for the LCD 8 is 3 amp resistive for 24 VAC Electrical Shock Fire Hazard CON...

Страница 2: ...enclosure Verifying system functionality after installation or when troubleshooting used to require spray circuit cooler or ice for controller activation The Sno TestTM feature eliminates this need b...

Страница 3: ...that it may be correctly processed upon receipt at Environmental Technology For more information about replacement parts or for a replacement Data Sheet or Manual please visit http www networketi com...

Страница 4: ...s off and the cup heaters energize for ten seconds Finally both are off for another ten seconds During this time the green LED blinks slowly one 1 second on one 1 second off Normal operation follows W...

Страница 5: ...ve 17 F but it enters the Lockout state instead if the temperature is below 17 F Additionally this Lockout state is entered if the temperature falls below 17 F during an automatic hold on cycle If the...

Страница 6: ...across this switch Figure 6 to start a hold on cycle or to terminate a running hold on cycle The magnetic switch determines whether the user s action swipes or holds the magnet during LCD 8 con gurat...

Страница 7: ...t is simply too cold to make operation practical The factory default low temperature lock out setting is Off meaning that the unit will try to activate the heaters regard less of ambient temperature S...

Страница 8: ...ensure sensing grid is dry and ambient air temperature is above 38 F 3 3 C then repeat this step 1 2 3 TO ENTER THE CONFIGURATION PROCESS The unit will ash the values of the three Field parameters in...

Страница 9: ...imer 0 1 3 default or 5 hours con gured by magnetic reed switch Set point temperature Off moisture only 36 F 38 F default 38 F con gured by magnetic reed switch INTERFACE Status indicators SUPPLY gree...