INSTALLATION AND OPERATION MANUAL  |  

HOLD-ON TIME

Hold-on time refers to the number of hours that the heaters will 

continue to operate once the unit no longer detects 

precipitation. Hold-on time ensures that not only is all the snow 

melted from the protected surface, but also that the system 

continues to dry and evaporate the surface without refreezing. 

The factory default hold-on time setting is 3 hours.

TEMPERATURE SET-POINT

The temperature set-point refers to the temperature at which 

the LCD-8 activates the heaters given the presence of moisture. 

When set to its default, “Off,” the controller activates the 

heaters based only on the presence of moisture at any 

temperature. The factory default temperature set point is 38°F 

(3.33°C).

LOW TEMPERATURE LOCK-OUT

The low temperature lock-out function disables unit operation 

in temperatures less than 17°F (–8.33°C) in those climates or 

during those seasons where it is simply too cold to make 

operation practical. The factory default low temperature 

lock-out setting is Off, meaning that the unit will try to activate 

the heaters regard- less of ambient temperature.

SETTING THE CONFIGURATION

FIELD 1: HOLD-ON TIME

1: off

2: 1 hour

3: 3 hours*

4: 5 hours

VALUES

FIELD 2: OPERATING TEMPERATURE

VALUES 1: none

(precipitation sensor)

2: 36°F / 2.2°C

3: 38°F / 3.3°C*

4: 40°F / 4.4°C

FIELD 3: LOW TEMPERATURE LOCKOUT

VALUES 1: disabled*

2: enabled

There  are  three  fields  available  for  configuration.  Each  has 

several numerical values possible, as follows:

* Default values

LCD-8 CONFIGURATION

The user is able to configure three operating parameters on the 

Snow Switch Model LCD–8.

These are:

The definitions of each of these parameters, as well as how to 

determine their current setting and how to change those 

settings, will be explained in this section of the manual.

The hold-on time in hours;

The temperature setpoint in degrees Fahrenheit; and

Low temperature lock-out operation.

2 second pause

4 second pause; to top

2 second pause

3 hour hold-on

38°F / 3.3°C

Low temperature

lockout disabled

FIGURE 7

LED response, default configuration

Содержание SNOW SWITCH LCD-8

Страница 1: ...ngle point of disconnect Size the circuit breaker in accordance with the size of the expected load The maximum current load for the LCD 8 is 3 amp resistive for 24 VAC Electrical Shock Fire Hazard CON...

Страница 2: ...enclosure Verifying system functionality after installation or when troubleshooting used to require spray circuit cooler or ice for controller activation The Sno TestTM feature eliminates this need b...

Страница 3: ...that it may be correctly processed upon receipt at Environmental Technology For more information about replacement parts or for a replacement Data Sheet or Manual please visit http www networketi com...

Страница 4: ...s off and the cup heaters energize for ten seconds Finally both are off for another ten seconds During this time the green LED blinks slowly one 1 second on one 1 second off Normal operation follows W...

Страница 5: ...ve 17 F but it enters the Lockout state instead if the temperature is below 17 F Additionally this Lockout state is entered if the temperature falls below 17 F during an automatic hold on cycle If the...

Страница 6: ...across this switch Figure 6 to start a hold on cycle or to terminate a running hold on cycle The magnetic switch determines whether the user s action swipes or holds the magnet during LCD 8 con gurat...

Страница 7: ...t is simply too cold to make operation practical The factory default low temperature lock out setting is Off meaning that the unit will try to activate the heaters regard less of ambient temperature S...

Страница 8: ...ensure sensing grid is dry and ambient air temperature is above 38 F 3 3 C then repeat this step 1 2 3 TO ENTER THE CONFIGURATION PROCESS The unit will ash the values of the three Field parameters in...

Страница 9: ...imer 0 1 3 default or 5 hours con gured by magnetic reed switch Set point temperature Off moisture only 36 F 38 F default 38 F con gured by magnetic reed switch INTERFACE Status indicators SUPPLY gree...

Страница 10: ...ressed or implied with respect to the contents of this publication or the products that it describes and speci cally disclaims any implied warranties of merchantability or tness for any particular pur...

Отзывы: