Condensate Piping
This water heater is a high ef
ciency, fully condensing appliance which produces condensate during operation.
The water heater incorporates a collection and removal system of condensate which must be properly drained in
order to ensure proper operation of this appliance.
Please use PVC or CPVC for the drain line.
Do not use steel, black iron, or any other material which can
corrode when contacting with condensate water.
Keep the length of the drain pipe as short as possible. Long runs, or applications where the nearest drain is
above the water heater, will require the use of a condensate pump. Size the pump to allow for a maximum
condensate discharge of 2 GPH from the water heater.
Horizontal runs must be sloped 1/4" per foot towards the drain or condensate pump.
Be sure to check that condensate is freely flowing from the drain piping after the system has been installed.
Condensate will begin
owing out of the water heater within 15 minutes after operation has started.
□
□
□
□
Condensate Piping to Floor Drain
Condensate Piping to Condensate Pump
Eternal Condensate Neutralizer
Condensate Pump
Eternal Condensate Neutralizer
□
CAUTION
!
The end of the drain pipe must not be submerged in water or blocked in any way.
Taking measures to prevent the condensate drain lines from freezing is recommended (insulation, heat tape, electric
heater, etc.)
!
15
1/2" CPVC
1/2" CPVC
Содержание GU125T
Страница 3: ...3 Included Accessories Optional Accessories...
Страница 5: ...5 Dimensions GU125T 518 11 12 1125 GU160T 518 11 12 1160...
Страница 6: ...6 Dimensions GU125T 518 11 12 1125 GU160T 518 11 12 1160...
Страница 7: ...7 Dimensions GU125T 518 11 12 1125 GU160T 518 11 12 1160...
Страница 35: ...35 Wiring and Connection Diagram Wiring Diagram MODEL GU125T 518 11 12 1125 GU160T 518 11 12 1160...
Страница 38: ...38 The stand assembly installation manual...
Страница 39: ...39 The stand assembly installation manual...