Final Installation and Power Up
23
enclosure, or only a Paradigm Station Repeater module (P-REP) in the top module slot with an
blank module below.
4:
Install either the ERn blank option module, the ERn ethernet switch Module (ERn-NET), or the
Redundant Power Supply (ERn-RPS) in the lower option module slot.
a: If installing the ERn ethernet switch Module (ERn-NET) or the Redundant Rack Power Supply
(ERn-RPS) module in the option module slot, be certain you have completed the installation
requirements. See
.
5:
Install blank module in any unused module slot in the enclosure to maintain the required
convection cooling requirements.
Note:
Neither the Redundant Power Supply (ERn-RPS) nor the Ethernet Switch module
(ERn-NET) are supported in an ERn4 enclosure at 230 VAC. Instead, an ERn4 at
230 VAC is shipped from the factory with a rack power supply installed in the top
(normal) position and in the lower option module slot as standard.