ETC Installation Guide

Contact and Demand Response Interfaces

Echo Contact and Demand Response Interfaces

 Page 8 of 8

ETC

• For an Output Interface, set the Zone number (1 through 16 available) 

for the first output on the interface. The remaining outputs will be 
assigned consecutive zone numbers. The zone number does not 
apply while in Custom configuration mode.

Power Up

All EchoConnect terminations in the system must be made before applying 
power to the system and interface. When the interface is powered up, the 
power LED will indicate in blue.

LED States

Input and Demand Response Interface

When a contact is closed, the related status LED will illuminate.

Output Interface

When the normally open contact is closed, the corresponding status LED will 
illuminate.

Reset Device

Using a ball point pen, press the [Reset] button to reset the interface, cycling 
power and restoring the device to normal operation.

Reset to Factory Defaults

Using a ball point pen, press the [Reset] button for ten seconds to reset the 
interface to factory defaults. The power LED will flash when the device has 
been restored to its factory defaults.

Remove the Interface from DIN rail

If for any reason you need to remove the interface from the DIN rail, follow 
these instructions:

1:

Shut off power from the unit. 

2:

Label, then disconnect all wiring and cap off as necessary.

3:

Insert a flat blade screwdriver into the clip on top of the interface, 
slide the unit straight up, then pivot the top edge off the DIN rail.

Note: When setting the first zone number, be careful to 

allow enough in the range for all outputs in the 

interface. For example, if you set the first zone to 

address 15, the remaining output contacts on the 

controller will be assigned to and respond as Zone 16.

Содержание Unison Echo

Страница 1: ...closures to trigger control actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface p...

Страница 2: ...ecommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not exceed 1 640 feet 500 m Electrical Requirements Echo...

Страница 3: ...ts of terminals normally open N O normally closed N C and common COM for connection of output relays Terminals accept 24 12 AWG 0 2 mm2 4 mm2 wire Each output includes a corresponding onboard LED to i...

Страница 4: ...terface plus one ESD ground wire 1 Strip 3 8 9 10 mm of insulation from the bare end of the Belden 8471 or equivalent wires and the ESD ground wire 2 Loosen the three screw terminals ground on the Ech...

Страница 5: ...inals 3 Insert the common wire into the COM terminal and the output wire into the respective NO or NC terminal 4 Secure the screws firmly onto each wire Set Configuration Mode The configuration mode s...

Страница 6: ...d zone is non zero the corresponding relay output will be closed When the intensity of an assigned zone is equal to zero the corresponding relay will be open By default all odd numbered presets when a...

Страница 7: ...Space and Address Zone Start Interface devices participate in an Echo control system using the configured Space and Address Zone which are selectable using the rotary switches on the front of the unit...

Страница 8: ...vice Using a ball point pen press the Reset button to reset the interface cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset bu...

Отзывы: