ETC Installation Guide

Contact and Demand Response Interfaces

Echo Contact and Demand Response Interfaces

 Page 2 of 8

ETC

Prepare for Installation

Ambient Environment

For indoor, commercial controls use only. Supports plenum rating.

• Operating temperature 0-50°C, 0-95% non-condensing humidity.

Compliance

• UL/cUL listed, supporting use in a plenum space
• CE compliant
• WEEE marked

For use with ETC dimming and relay products.

Control Requirements

EchoConnect

Echo interface devices require EchoConnect

®

, Belden 8471 (or equivalent) 

plus one ESD ground wire, supporting control signal between the device 
and the connected Echo control system.

EchoConnect is a bidirectional protocol that uses one pair of wires (data+ 
and data-). ETC recommends using Belden 8471 (or approved equal) Class 2 
wire.

The total combined length of an EchoConnect wire run (using Belden 8471, 
or equal) may not exceed 1,640 feet (500 m).

Electrical Requirements

Echo interface devices require 24 VDC (Class 2) external power in addition 
to EchoConnect requirements. This auxiliary power is provided to the input 
connector by an external supply. The unit draws a maximum of 40mA 
during normal operation.

This connection is provided on a two position terminal, labeled 24 VDC, and 
accepts 24-12 AWG (0.2-4 mm

2

) wires (typically black and red wire pair).

Note: Installation should follow all local codes and standard 

electrical practices.

Note: NEC Class 2 product are to be wired in accordance with 

NEC Article 725 and local jurisdiction requirements.
All power and control wiring should be installed and 

terminated by a qualified installer and should follow 

standard wiring installation practices.

Содержание Unison Echo

Страница 1: ...closures to trigger control actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface p...

Страница 2: ...ecommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not exceed 1 640 feet 500 m Electrical Requirements Echo...

Страница 3: ...ts of terminals normally open N O normally closed N C and common COM for connection of output relays Terminals accept 24 12 AWG 0 2 mm2 4 mm2 wire Each output includes a corresponding onboard LED to i...

Страница 4: ...terface plus one ESD ground wire 1 Strip 3 8 9 10 mm of insulation from the bare end of the Belden 8471 or equivalent wires and the ESD ground wire 2 Loosen the three screw terminals ground on the Ech...

Страница 5: ...inals 3 Insert the common wire into the COM terminal and the output wire into the respective NO or NC terminal 4 Secure the screws firmly onto each wire Set Configuration Mode The configuration mode s...

Страница 6: ...d zone is non zero the corresponding relay output will be closed When the intensity of an assigned zone is equal to zero the corresponding relay will be open By default all odd numbered presets when a...

Страница 7: ...Space and Address Zone Start Interface devices participate in an Echo control system using the configured Space and Address Zone which are selectable using the rotary switches on the front of the unit...

Страница 8: ...vice Using a ball point pen press the Reset button to reset the interface cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset bu...

Отзывы: