ETC Installation Guide

Contact and Demand Response Interfaces

Echo Contact and Demand Response Interfaces

 Page 7 of 8

ETC

Demand Response Interface

Inputs control Spaces determined by settings applied in the EchoAccess 
Mobile App.

Output Interface 

Relay outputs are controlled by the status of Presets 1-4 respectively.

• When the status of an assigned preset is active, the corresponding 

relay output will be closed.

• When the status of an assigned preset is inactive, the corresponding 

relay will be open.

Aside from the default behaviors when the configuration mode switch set 
to Custom, complete configuration of the Output Interface is supported by 
the EchoAccess Mobile App. For detailed information about custom 
configuration options available using EchoAccess, reference the EchoAccess 
Mobile App integrated help system.

Set Space and Address / Zone Start

Interface devices participate in an Echo control system using the configured 
Space and Address / Zone which are selectable using the rotary switches on 
the front of the unit.

By default, these switches are set to Space 1, Address / Zone 1.

1:

Set the Space for this device (1 through 16 available). All control 
inputs from the connected stations, sensors, and other controls are 
shared by all devices within the selected space. This setting applies 
regardless of the selected configuration mode (Basic or Custom).

2:

Set the Address / Zone:
• For an Input Interface, set the Address (1 through 16 available) 

which identifies the device in the selected space. This setting 
always applies.

Note: Each Echo space can only have one assigned demand 

response input.

Note: For the Demand Response Interface, setting the Space 

address determines the four consecutive spaces that 

will be controlled. A value higher than 13 will result in 

control of only Spaces 14, 15, and 16.

Note: Do not duplicate a device address within the same 

space.

Содержание Unison Echo

Страница 1: ...closures to trigger control actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface p...

Страница 2: ...ecommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not exceed 1 640 feet 500 m Electrical Requirements Echo...

Страница 3: ...ts of terminals normally open N O normally closed N C and common COM for connection of output relays Terminals accept 24 12 AWG 0 2 mm2 4 mm2 wire Each output includes a corresponding onboard LED to i...

Страница 4: ...terface plus one ESD ground wire 1 Strip 3 8 9 10 mm of insulation from the bare end of the Belden 8471 or equivalent wires and the ESD ground wire 2 Loosen the three screw terminals ground on the Ech...

Страница 5: ...inals 3 Insert the common wire into the COM terminal and the output wire into the respective NO or NC terminal 4 Secure the screws firmly onto each wire Set Configuration Mode The configuration mode s...

Страница 6: ...d zone is non zero the corresponding relay output will be closed When the intensity of an assigned zone is equal to zero the corresponding relay will be open By default all odd numbered presets when a...

Страница 7: ...Space and Address Zone Start Interface devices participate in an Echo control system using the configured Space and Address Zone which are selectable using the rotary switches on the front of the unit...

Страница 8: ...vice Using a ball point pen press the Reset button to reset the interface cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset bu...

Отзывы: