ETC Installation Guide

Contact and Demand Response Interfaces

Echo Contact and Demand Response Interfaces

 Page 3 of 8

ETC

Input and Demand Response Interface Wire Terminations

The Input and Demand Response Interfaces provide four sets of terminals 
(“In” and “V out”) for connection to a momentary (Input Interface only) or 
maintained contact input. Terminals accept 24-12 AWG (0.2 mm

2

-4 mm

2

wire.

Each input supports wet or dry contact closures and includes a related 
onboard LED to indicate contact status.

Output Interface Wire Terminations

The Contact Output Interface provides four sets of terminals (normally open 
“N.O.”, normally closed “N.C.”, and common “COM”) for connection of 
output relays. Terminals accept 24-12 AWG (0.2 mm

- 4 mm

2

) wire.

Each output includes a corresponding onboard LED to indicate the normally 
open status of the relay.

Installation

Install to DIN rail

Note: Input terminals accept 3 - 24 VDC, and support 2,000 

feet (610 m) of 18 AWG (1 mm

2

) wire (round trip wire 

to the device) when using 24 VDC.

Note: Each output is rated for 2A at 30 VAC or 30 VDC.

2

3

1:

Ensure the section of DIN rail to be used is mounted 
securely according to the manufacturer’s 
requirements. DIN rail is provided by others. 

2:

Hook the bottom of the Echo interface under the lower 
DIN rail as shown. 

3:

Pivot the interface up and depress until the top clip 
seats completely onto the DIN rail.

Содержание Unison Echo

Страница 1: ...closures to trigger control actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface p...

Страница 2: ...ecommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not exceed 1 640 feet 500 m Electrical Requirements Echo...

Страница 3: ...ts of terminals normally open N O normally closed N C and common COM for connection of output relays Terminals accept 24 12 AWG 0 2 mm2 4 mm2 wire Each output includes a corresponding onboard LED to i...

Страница 4: ...terface plus one ESD ground wire 1 Strip 3 8 9 10 mm of insulation from the bare end of the Belden 8471 or equivalent wires and the ESD ground wire 2 Loosen the three screw terminals ground on the Ech...

Страница 5: ...inals 3 Insert the common wire into the COM terminal and the output wire into the respective NO or NC terminal 4 Secure the screws firmly onto each wire Set Configuration Mode The configuration mode s...

Страница 6: ...d zone is non zero the corresponding relay output will be closed When the intensity of an assigned zone is equal to zero the corresponding relay will be open By default all odd numbered presets when a...

Страница 7: ...Space and Address Zone Start Interface devices participate in an Echo control system using the configured Space and Address Zone which are selectable using the rotary switches on the front of the unit...

Страница 8: ...vice Using a ball point pen press the Reset button to reset the interface cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset bu...