background image

ETC Installation Guide

Contact and Demand Response Interfaces

Echo Contact and Demand Response Interfaces

 Page 6 of 8

ETC

Demand Response Interface:

Activates Demand Response, affecting up four consecutive Echo Spaces, 
starting with the interface Space rotary switch setting.

Example: Setting the Space switch to 3 results in control of Spaces 3, 4, 5, 
and 6. A value higher than 13 will result in control of only Spaces 14, 15, 
and 16.

Functionality:

• a closed contact means the designated space is in active Demand 

Response state

• an open contact means Demand Response is inactive

Output Interface:

Relay outputs are controlled by Zones 1-4 respectively (when the Zone dial is 
set to its default setting of 1). Changing the Zone dial will alter the starting 
Zone. Reference the related Note on the bottom of page 7. 

• When the intensity of an assigned zone is non-zero the 

corresponding relay output will be closed.

• When the intensity of an assigned zone is equal to zero the 

corresponding relay will be open.

• By default, all odd numbered presets, when activated, will close all 

relay outputs and all even numbered presets, when activated, will 
open all relay outputs. This is true until the preset is re-recorded with 
new values.

Custom

Custom configuration mode applies the following default behaviors until 
changed using the EchoAccess Mobile App:

Input Interface 

Inputs control Presets 1-4 respectively, using maintained input mode where:

• closing contact activates a preset
• opening a contact deactivates a preset

Note: Each Echo space can only have one assigned demand 

response input.

Note: Functionality varies depending on whether the 

normally open or normally closed contact terminal is 

utilized. The default behaviors listed below are 

assuming a normally open installation. The normally 

closed contact provides inverted behavior, its status 

always the opposite of the normally open contact.

Содержание Unison Echo

Страница 1: ...closures to trigger control actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface p...

Страница 2: ...ecommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not exceed 1 640 feet 500 m Electrical Requirements Echo...

Страница 3: ...ts of terminals normally open N O normally closed N C and common COM for connection of output relays Terminals accept 24 12 AWG 0 2 mm2 4 mm2 wire Each output includes a corresponding onboard LED to i...

Страница 4: ...terface plus one ESD ground wire 1 Strip 3 8 9 10 mm of insulation from the bare end of the Belden 8471 or equivalent wires and the ESD ground wire 2 Loosen the three screw terminals ground on the Ech...

Страница 5: ...inals 3 Insert the common wire into the COM terminal and the output wire into the respective NO or NC terminal 4 Secure the screws firmly onto each wire Set Configuration Mode The configuration mode s...

Страница 6: ...d zone is non zero the corresponding relay output will be closed When the intensity of an assigned zone is equal to zero the corresponding relay will be open By default all odd numbered presets when a...

Страница 7: ...Space and Address Zone Start Interface devices participate in an Echo control system using the configured Space and Address Zone which are selectable using the rotary switches on the front of the unit...

Страница 8: ...vice Using a ball point pen press the Reset button to reset the interface cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset bu...

Отзывы: