background image

ETC Installation Guide

Contact and Demand Response Interfaces

Echo Contact and Demand Response Interfaces

 Page 5 of 8

ETC

2:

Loosen the “In” terminal for the contact input and insert the positive 
contact voltage wire.

3:

Terminate the contact return wire into the negative “-” terminal of 
the
24 VDC input. Alternative wiring termination methods may be 
required to accommodate multiple terminations. 

4:

Secure the screws firmly onto each wire for all terminals. 

Connect Output Wiring (Output Interface only)

Terminals accept 24-12 AWG (0.2-4 mm

2

)

1:

Strip 3/8” (9-10 mm) of insulation from each wire.

2:

Determine the type of output required, normally open (NO) or 
normally closed (NC), then loosen the respective output and COM 
terminals.

3:

Insert the common wire into the “COM” terminal and the output 
wire into the respective “NO” or “NC” terminal.

4:

Secure the screws firmly onto each wire.

Set Configuration Mode

The configuration mode switch allows selection between Basic and Custom 
configurations of the interface. Basic is the factory default setting.

Basic

Basic configuration mode applies the following default behaviors:

Input Interface:

Inputs control Presets 1-4 respectively, using momentary input mode where 
the closure behaves similar to an Echo Inspire station.

• close / open event (push) executes a preset toggle
• holding the contact closed (hold) performs a space raise
• closing the closure twice (in rapid succession) performs a preset 

toggle with 1/2 second override timing

Note: Particularly when considering machine driven 

applications, ETC recommends a minimum of 500 ms 

between any input changes to ensure transitions are 

reliably applied.

Содержание Unison Echo

Страница 1: ...closures to trigger control actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface p...

Страница 2: ...ecommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not exceed 1 640 feet 500 m Electrical Requirements Echo...

Страница 3: ...ts of terminals normally open N O normally closed N C and common COM for connection of output relays Terminals accept 24 12 AWG 0 2 mm2 4 mm2 wire Each output includes a corresponding onboard LED to i...

Страница 4: ...terface plus one ESD ground wire 1 Strip 3 8 9 10 mm of insulation from the bare end of the Belden 8471 or equivalent wires and the ESD ground wire 2 Loosen the three screw terminals ground on the Ech...

Страница 5: ...inals 3 Insert the common wire into the COM terminal and the output wire into the respective NO or NC terminal 4 Secure the screws firmly onto each wire Set Configuration Mode The configuration mode s...

Страница 6: ...d zone is non zero the corresponding relay output will be closed When the intensity of an assigned zone is equal to zero the corresponding relay will be open By default all odd numbered presets when a...

Страница 7: ...Space and Address Zone Start Interface devices participate in an Echo control system using the configured Space and Address Zone which are selectable using the rotary switches on the front of the unit...

Страница 8: ...vice Using a ball point pen press the Reset button to reset the interface cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset bu...

Отзывы: