Emergency Operation and Test
It is important to test ArcSystem emergency systems regularly because they are life safety devices.
NOT SELF-TESTING PER ANSI/NFPA 101 - This equipment is not self-testing in conformance with
the Life Safety Code, ANSI/NFPA 101. ANSI/NFPA 101 Life Safety Code requires testing of life
safety devices every 30 days.
To test the emergency functionality of this device, disconnect the sense circuit.
WARNING:
RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all
power to the system before installation, maintenance, cleaning, or any other
system modification could result in serious injury or death.
AVERTISSEMENT :
RISQUE DE MORT PAR DÉCHARGE ÉLECTRIQUE! Négliger
de débrancher toutes les sources d’alimentation du système avant l’installation,
l’entretien, le nettoyage ou toute autre modification du système peut causer
des blessures graves ou la mort.
De-energize main feed to ArcSystem and follow appropriate Lockout/Tagout
procedures as mandated by NFPA 70E. It is important to note that electrical
equipment such as breaker panels can present an arc flash hazard if improperly
serviced. This is due to the high amounts of short-circuit current available on
the electrical supply to this equipment. Any work must comply with OSHA Safe
Working Practices.
CAUTION:
This equipment is provided with more than one supply source. To
reduce the risk of electric shock, disconnect both normal and emergency sources
within this unit before servicing any equipment connected to this unit.
ATTENTION :
Cet équipement possède plus d’une source d’alimentation. Pour
réduire les risques de décharge électrique, débrancher les sources d’alimentation
normale et de secours dans l’unité avant de faire l’entretien d’un équipement
branché à cette unité.
Test the ArcSystem emergency system as described:
1.
Turn off power at the normal circuit breaker.
2.
Test the system per ANSI/NFPA 101 Life Safety Code.