ETC ArcSystem Pro One-Cell Скачать руководство пользователя страница 25

ETC Installation Guide

Pro One-Cell

Pro One-Cell

Page 25 of 29

ETC

Parameter

RDM PID

Value

Notes

DMX Start Address

0x00F0

Range = 001 to 512

Default is 001. The upper limit for the D4 Series
drivers is 508.

DMX Personality

0x00E0

1 or 2

Default is 2. This parameter sets the number of
DMX channels available on a D4 Series driver.

Set to 1 sets DMX personality to multi-channel.

Set to 2 sets DMX personality to single-
channel.

Identify Device

0x1000

0 for stop identify, 1 for start
identify

Set to 1 causes output(s) and LEDs of the unit to
blink in a one second on, one second off pattern.

Minimum Level

0x0341

0 to 255

Default is 99%. The luminaire will not accept a
Minimum Level that is higher than the Maximum
Level.

Maximum Level

0x0342

0 to 255

Default is 100%. The luminaire will not accept a
Maximum Level that is lower than the Minimum
Level.

Curve

0x0343

1, 2, or 3

Set to 1 is the Default Tungsten Curve (aka
D04A)

Set to 2 is Linear

Set to 3 is Square Law

Curve Description

0x0344

Get returns an ASCII text string.

Output Response Time

0x0345

0x01 1000 ms/100 steps

0x02 900 ms/90 steps

0x03 800 ms/80 steps

0x04 700 ms/70 steps

0x05 600 ms/60 steps

0x06 500 ms/50 steps

0x07 400 ms/40 steps

0x08 300 ms/30 steps

0x09 250 ms/25 steps

0x0A 200 ms/20 steps

0x0B 100 ms/10 steps

0x0C 50 ms/5 steps

0x0D 0 ms/0 steps

Default is 500ms/50 steps. This parameter
controls dimming up in level.

Output Response Time
Down

0x8030

Default is 500 ms/50 steps. This parameter
controls dimming down in level. Set 0x00 to set
the Output Response Time Down to the same
setting as Output Response Time.

Output Response Time
Description

0x0346

Get returns an ASCII text string.

Modulation Frequency

0x0347

32-bit unsigned integer
representation of the frequency
in Hz

300 for 300 Hz

600 for 600 Hz

1200 for 1.2 kHz

19200 for 19.2 kHz

Default is 300 Hz.

Modulation Frequency
Description

0x0348

Get returns an ASCII text string.

Restore Factory Defaults

0x0090

Set resets the luminaire configuration to default
settings.

Software Version Label

0x00C0

Get returns the current software version as an
ASCII text string.

Bootloader Version Label

0x00C2

Get returns the current bootloader version as an
ASCII text string.

Updating the Luminaire Software

ETC recommends using UpdaterAtor software to manage software updates. For more information on
UpdaterAtor, download the

UpdaterAtor Software Quick Guide

for free from

etcconnect.com

.

Содержание ArcSystem Pro One-Cell

Страница 1: ...ystem products with ArcMesh can be controlled using wired DMX or the wireless ArcMesh protocol ArcSystem products without ArcMesh can be configured for RDM control This manual provides step by step in...

Страница 2: ...ount with single axis tilt yoke mount version with single axis tilt beam angle options 19 24 37 60 ArcSystem Pro One Cell High Output external 100 277 V D1 HO driver required ideal for long throw 100...

Страница 3: ...One Cell Small luminaire The D1 HO Driver provides up to 100 W to a single One Cell High Output luminaire The D2 Driver supports one or two One Cell Micro luminaires and provides up to 10 W per outpu...

Страница 4: ...s can be configured to be UL924 listed when wired into an existing emergency response system See Emergency System One Cell Installation on page 19 Install the ArcSystem D1 D2 or D4 Series driver in a...

Страница 5: ...NING Do not mix 120 V and 277 V between the sense and emergency feeds AVERTISSEMENT Ne pas inverser les alimentations 120 V et 277 V entre les alimentations de d tection et de secours WARNING Sense no...

Страница 6: ...al supply to this equipment Any work must comply with OSHA Safe Working Practices WARNING Circuits that are installed without an accessible power disconnect device cannot be serviced or operated safel...

Страница 7: ...ne Cell Micro luminaires The D4 driver can control up to four ArcSystem Pro One Cell or Pro One Cell Small luminaires Up to 32 drivers can be installed on one hard wired line of DMX The following illu...

Страница 8: ...ps screwdriver Four 10 screws and other mounting hardware as needed Note Mounting hardware and installation location must support the weight of the driver conduit hardware and all cable required for i...

Страница 9: ...5 Nm 3 5 4 4 in lb Note Maximum supported wire length between One Cell luminaires and D1 Series and D2 Series drivers is 15 m 49 ft Maximum supported wire length between any load and a D4 Series drive...

Страница 10: ...can extend through the ceiling opening so that the driver and luminaire can be inspected and serviced when needed Note Use suitable conduit where required by national and local codes Note Drivers may...

Страница 11: ...One Cell luminaires Luminaire Minimum Hole Diameter Pro One Cell 16 5 cm 6 1 2 in Pro One Cell High Output 17 0 cm 6 11 16 in Pro One Cell Small 9 5 cm 3 3 4 in Pro One Cell Micro 7 6 cm 3 in Note If...

Страница 12: ...inaire Wiring of the driver consists of wiring power and data DMX to the driver for your luminaire and then running power out to the luminaire from the driver If you are installing emergency system dr...

Страница 13: ...One Cell Page 13 of 29 ETC Output type varies by model A B C S1 S2 S3 S4 LED1 LED2 LED3 LED4 Switch blocks D4 Driver A Constant Current with Molex connectors B Constant Current with terminal outputs C...

Страница 14: ...ou de r parer les circuits install s sans qu un dispositif de d connexion de l alimentation ne soit accessible 1 Make sure power is off at the main circuit breaker 2 See Wire and Terminal Specificati...

Страница 15: ...10 m 33 ft 1 Install the ceiling with the prepared mounting hole for the luminaire 2 Run the luminaire cable through the previously installed screw clamp conduit connector at one of the driver knockou...

Страница 16: ...and Data plus an ISO ground common ETC recommends Cat5e or better minimum 24 AWG conductors terminated to T568B standard Up to 32 D1 D2 or D4 series drivers can be connected per DMX run DMX Connectio...

Страница 17: ...tage CV model driver Switch 1 sets the current output threshold ON 400 mA OFF 600 mA Switches 2 through 5 control the DMX channel assigned to the output Switch 6 enables emergency functionality Switch...

Страница 18: ...DU DRIVER DISPOSITIF LECTRONIQUE DE PUISSANCE WARNING Adjustable ArcSystem Pro One Cell fixtures and adjustable ArcSystem Pro One Cell Small fixtures are suitable for Non Fire Rated installations ONLY...

Страница 19: ...s those of the standard ArcSystem Complete the installation as follows referencing the following sections for any additional installation details before wiring the power Preparing to Install the Drive...

Страница 20: ...ge 20 of 29 ETC Output type varies by model A B C S1 S2 S3 S4 LED1 LED2 LED3 LED4 Switch blocks SENSE SENSE D4 Emergency Driver A Constant Current with Molex connectors B Constant Current with termina...

Страница 21: ...ND terminal and tighten the screw 4 Insert the neutral wire typically white into the NEUTRAL N terminal and tighten the screw 5 Connect the line wire typically black into the LINE L terminal and tight...

Страница 22: ...o not change the switch 1 settings on a D4 Constant Voltage CV model driver Switch 1 sets the current output threshold ON 400 mA OFF 600 mA Switches 2 through 5 control the DMX channel assigned to the...

Страница 23: ...or normal use During normal use after commissioning is complete ArcSystem luminaires will light if the DMX Control level is greater than 0 DMX System Control ArcSystem with ArcMesh can be installed an...

Страница 24: ...es RDM Values Manufacturer ID 0x6574 Electronic Theatre Controls Model IDs Product Type Description Model ID ArcSystem Pro One Cell or ArcSystem Pro One Cell Small D1 Driver 0x1201 D1 Emergency Driver...

Страница 25: ...steps 0x04 700 ms 70 steps 0x05 600 ms 60 steps 0x06 500 ms 50 steps 0x07 400 ms 40 steps 0x08 300 ms 30 steps 0x09 250 ms 25 steps 0x0A 200 ms 20 steps 0x0B 100 ms 10 steps 0x0C 50 ms 5 steps 0x0D 0...

Страница 26: ...avant d effectuer un nettoyage ou un entretien WARNING Circuits that are installed without an accessible power disconnect device cannot be serviced or operated safely AVERTISSEMENT Il est imprudent d...

Страница 27: ...tion du syst me peut causer des blessures graves ou la mort De energize main feed to ArcSystem and follow appropriate Lockout Tagout procedures as mandated by NFPA 70E It is important to note that ele...

Страница 28: ...ance ARCPD1DM ArcSystem D1 Driver cULus Conforms to UL 8750 Certified to CSA C22 2 No 250 13 EU CE Certified FCC compliant ARCPD1DRDMM ArcSystem D1 RDM Driver ARCPD1HDM ArcSystem D1 High Output Driver...

Страница 29: ...cy Driver with Two Pin Terminals ARCPED4DCVTM ArcSystem D4 Constant Voltage Emergency Driver with Two Pin Terminals ARCPED4DCVTRDMM ArcSystem D4 Constant Voltage Emergency Driver with Two Pin Terminal...

Отзывы: