Cleaning and maintenance
Maintenance (expert)
31
Adjustment requires the removal of the combustion
chamber door. To do so, open the combustion
chamber door, lift it slightly, remove it and carefully
place it next to the boiler.
1
Closing roller mount
2
Hinge
Loosen the flange nuts (top and bottom) on the hinge
and the closing roller mount and evenly make the gap
to the boiler a bit smaller.
Fig. 2-67: Reduce gap
Tighten the flange nuts. Attach the door and check
whether it closes fully. If not, repeat the process.
Fig. 2-68: Checks
Always adjust the hinges and the closing roll-
er mount so that the seal is evenly compressed.