Configuration
21
Assigning a terminal for the optional solenoid
valve
This step is only necessary if the fresh water
module is installed in the flow between the heat
producer and the buffer, meaning that a solenoid valve
is required. The solenoid valve is connected to the
circuit board [EM-C] at the terminal [S102 LZ] and
must be assigned manually.
Assigning terminal
1. In the [Selected function blocks] field, first select
the function block of the fresh water module [FWM
(FWM 2pumps)].
2. Double tap at the buffer pump [Buffer pump]. A
window opens.
3. Select in the lower window the terminal [S102 LZ]
at the board [EM-C] and add it with [Connect].
4. Close the window using the [Close] button.
Installing a configuration
Finish by pressing [Apply] to install the configuration.
The configuration will then be adopted and the
software restarted.