42
www.eta.co.at
Installing flue gas recirculation
Installation
9.3
Installing flue gas recirculation
Installing the actuator
Insert the adapter into the actuator. Ensure the correct
position, the slit must be 90° offset to the screw on the
actuator.
Fig. 9-8: Adapter
Turn the actuator in the closed position (see sticker).
Also turn the air valve shaft to the fully closed position.
Place the air valve on the shaft and fix it in the actuator
with the screw.
Fig. 9-9: Actuator
Fig. 9-10: Screw
Then connect the actuator to the line already laid (on
the top of the boiler).
Fig. 9-11: Electrically connecting the actuator