31
3. INSTALLATION INSTRUCTIONS
“T” section package, firestops (where needed), insulation
shield, roof flashing, chimney cap, etc. maintain proper
clearances to the structure as recommended by the
manufacturer. The chimney must be the required height
above the roof or other obstructions for safety and proper
draft operation.
Connection
through a
combustible
wall
Method A
Using a minimum thickness 3.5” (90mm) brick and a 5/8”
(16mm) minimum wall thickness clay liner, construct a wall
pass-through. The clay liner must conform to ASTM C315
(Standard Specification for Clay Fire Linings) or equivalent.
Keep a minimum of 12” (305mm) of brick masonry
between the clay liner and wall combustibles. The clay liner
shall run from the brick masonry outer surface to the inner
surface of the chimney flue liner but not past the inner
surface. Firmly grout or cement the clay liner in place to the
chimney flue liner.
Содержание BakeHeart
Страница 34: ...34 of 161...
Страница 35: ...35 of 161...
Страница 42: ...42 of 161...
Страница 43: ...43 of 161...
Страница 52: ...52 of 161...
Страница 53: ...53 of 161...
Страница 60: ...60 of 161...
Страница 61: ...61 of 161...
Страница 70: ...70 of 161...
Страница 71: ...71 of 161...
Страница 75: ...75 of 161...
Страница 76: ...76 of 161...
Страница 77: ...77 of 161...
Страница 78: ...78 of 161...
Страница 79: ...79 of 161...
Страница 80: ...80 of 161...
Страница 81: ...81 of 161...
Страница 82: ...82 of 161...
Страница 83: ...83 of 161...
Страница 85: ...85 of 161...
Страница 86: ...86 of 161...
Страница 87: ...87 of 161...
Страница 94: ...94 of 161...
Страница 96: ...96 of 161...
Страница 97: ...97 of 161...
Страница 113: ......
Страница 114: ...Bakeheart and Warmheart Wood Fired Cook Stove Owner s Manual OMNI Test Laboratories Inc 0224WS009S 0224WS009E...
Страница 159: ......