background image

7

exaMPle 3: sPlit

Splitpoint 0° selected 

with heating curve part 1 

selected to 1.1 and heating 

curve part 2 selected to 

0.7 will increase flow temp 

from 38° to 42° at out-

door temp 0° compared to 

simple heating curve 0.9

exaMPle 4: Max/Min 

sPlit

Splitpoint 0° selected with 

heating curve part 1 selec-

ted to 1.1 and heating curve 

part 2 selected to 0.7 will 

increase flow temp from 38° 

to 42° at outdoor temp 0° 

compared to simple heating 

curve 0.9

 

Max limitation 50°C and min 

limitation 25°C added.

The following settings can be used for parallel translation of the characteris-

tic for certain time periods such as daytime and nighttime mode.

Menu 5.4 day correction  = Parallel translation of the characteristic

The day correction produces a parallel translation of the heating characteristic during 

the daytime operating hours, since depending on the outdoor temperature it is pos-

sible that the building may not be optimally heated with the set characteristic. If the 

characteristic is not optimised, the following situation may occur:
in hot weather - the spaces are too cold 

in cold weather - the spaces are too hot
In this case, one should gradually reduce the characteristic slope in steps of 0.2, each 

time raising the day correction by 2-4 °C. 

This procedure can be repeated several times as needed.

Setting range: from -10°C to 50°C / / Default: 5°C

Menu 5.5 night correction  = Parallel translation of the characteristic

The night correction produces a parallel translation of the heating characteristic 

during the nighttime operating hours. If a negative value is set for the night correction, 

the reference fl ow temperature is lowered accordingly during the nighttime operating 

hours. In this manner, primarily at night, but also during the day when no-one is at 

home, the room temperature is lowered, thus saving energy.
Example: A day correction of +5°C and a night correction of -2°C produces a refe-

rence flow temperature in nighttime operation that is 7°C lower. 

Setting range: from -30°C to 30°C / / Default: -2°C

Menu 5.6 coMfort teMPerature boost = Parallel translation of the 

characteristic

The comfort temperature boost is added to the set day correction. In this manner it 

is possible to carry out quick heating and/or a higher temperature in the living spaces 

at a certain time each day.

Setting range: from 0°C to 15°C / / Default: 0°C = off

Menu 5.7 reference/actual -

Permissible reference value undershoot of the heating value.

Settings range -10°C to -2 / Default: -2°C

Menu 5.8 reference/

Permissible reference value overshoot of the heating value.

Settings range 2°C to 20 / Default: 2°C

Menu 6 is activated when Heating circuit 2 is selected in menu 15.7.2
Note: Pump is activated when actual flow temp < target flow 2.

Menu 6.1 s/W day  

see Menu 5.1

Menu 6.2 s/W night 

see Menu 5.2

Menu 6.3 curVe 

see Menu 5.3 including curve examples.

Menu 6.4 day correction 

see Menu 5.4

Menu 6.5 night correction

 

see Menu 5.5

Menu 6.6 coMfort teMP bost

 

see Menu 5.6

Menu 7 is activated when Dom. Hot water is selected in menu 15.7.2

Menu 7.1 hot Water MiniMuM

Minimum domestic hot water temperature outside of the operating times.

Settings range 10°C to 80 / Default: 45°C

Menu 7.2 dhW target

Minimum DHW temperature during operating hours.

Settings range 10°C to 80°C / Default: 45°C

Menu 4.3 heat circuit reference  

If operating mode “Reference value” is selected,  (Menu 4.1), the reference flow tem-

perature has to be set here, regardless of the curve/outdoor temperature.

Settings range: 10 °C to 75 °C, Default: 30 °C

Menu 4.4 14 day reference  

If operating mode “14 day reference value” is selected (Menu 4.1), the reference flow 

temperature for each of the 14 days can be set here.
In the first menu 4.4.1 the starting time of the program is shown. To start the program, 

hit restart.
Set parameters for the heating circuit. 
Hitting “restart” again will reset the 14 day reference program and start it at day 1.

Menu 4.5 doMestic hot Water

Auto =   The Domestic Hot Water function is activated according to the schedule  in  

 

menu 3.5. 

On =  

The Domestic Hot Water function is always on. 

Off =  

The Domestic Hot Water function is always off

Menu 5.1 s/W day  = suMMer/Winter  changeoVer in daytiMe Mode

If this value is exceeded at outdoor sensor during the daytime mode times, the control-

ler automatically switches the heating circuit off = Summer mode.
If the outdoor temperature drops below this value, the heating circuit is switched on 

again = Winter mode. 

Setting range: from 0°C to 30°C / default setting: 18°C

In addition to the operating times in normal daytime operation, this setting is also 

valid for times with activated comfort temperature boost.

Menu 5.2 s/W night  =  suMMer/Winter changeoVer in nighttiMe Mode

If this value is exceeded at outdoor sensor during the nighttime mode times, the con-

troller automatically switches the heating circuit off = Summer mode.
If the outdoor temperature drops below this value, the heating circuit is switched on 

again = Winter mode.

Settings range: 0°C to  30°C / Default: 12°C

Menu 5.3 curVe  = sloPe of the characteristic heating curVe 

The characteristic curve is used to control the heat dissipation of the heating circuit 

relative to the outdoor temperature.
The demand for heat is different due to differences in the type of building/insulation/

type of heating/outdoor temperature. For this reason the controller can make use of 

a normal straight curve (Setting simple) or a split curve (Setting split).
In the simple setting the curve can be adjusted with the help of the graphic diagram. 

The slope is changed, and the calculated reference flow temperature is displayed 

for -20 °C.
If the split mode is selected, the characteristic curve is adjusted in 3 steps. First the 

standard slope has to be set, after that the split point and finally the steepness of the 

curve after the split. While adjusting the curve the steepness of the slope and the 

calculated reference flow temperature for -20 °C outdoor temperature is displayed. 

Splited curve is often selected to compensate. 

Settings range:  

Characteristic curve : simple or split / Default: simple 

Slope : 0.0...3.0 / Default: 0.8 

Splitpoint at outdoor temp.: +10°C...-10°C 

Angle: differs, depends on steepnes and split point

The diagram shows the influence of the selected characteristic curve steepness 

(standard curve) on the calculated reference flow temperature of the heating circuit. 

The correct curve is appointed by setting the intersection point of the calculated 

maximum flow temperature and the minimum outdoor temperature.
Maximum calculated flow temperature 60°C at minimum outdoor temperature accor-

ding to heat demand calculation -12°C.
The intersection results in a slope of 1.2.

exaMPle 1: siMPle

exaMPle 2: sPlit 

Splitpoint 0° selected with 

heating curve part 1 selec-

ted to 1.0 and heating curve 

part 2 selected to 0.8 will 

increase flow temp from 38° 

to 40° at outdoor temp 0° 

compared to simple heating 

curve 0.9

20

30

40

50

60

70

80

90

100

110

20

10

-10 -12

0

-20

-30

-40

-50

+15

+10

+5

−5

20

30

40

50

60

70

80

90

100

110

20

10

-10 -12

0

-20

+15

+10

−5

20

30

40

50

60

70

80

90

100

20

10

-10 -12

0

-20

-30

-40

-50

+15

+10

+5

−5

20

30

40

50

60

70

80

90

100

20

10

-10 -12

0

-20

+15

+10

+5

−5

+5

+0 °C

+0 °C

+0 °C

+0 °C

Da

y cor

rection

Flo

w t

em

per

atur

e °

 C 

 

Characteristic curve

Outdoor temperature ° C 

20

30

40

50

60

70

80

90

100

110

20

10

-10 -12

0

-20

-30

-40

-50

+15

+10

+5

−5

20

30

40

50

60

70

80

90

100

110

20

10

-10 -12

0

-20

+15

+10

−5

20

30

40

50

60

70

80

90

100

20

10

-10 -12

0

-20

-30

-40

-50

+15

+10

+5

−5

20

30

40

50

60

70

80

90

100

20

10

-10 -12

0

-20

+15

+10

+5

−5

+5

+0 °C

+0 °C

+0 °C

+0 °C

Flo

w t

em

per

atur

e °

 C 

 

Characteristic curve

Outdoor temperature ° C 

Da

y cor

rection

20

30

40

50

60

70

80

90

100

110

20

10

-10 -12

0

-20

-30

-40

-50

+15

+10

+5

−5

20

30

40

50

60

70

80

90

100

110

20

10

-10 -12

0

-20

+15

+10

−5

20

30

40

50

60

70

80

90

100

20

10

-10 -12

0

-20

-30

-40

-50

+15

+10

+5

−5

20

30

40

50

60

70

80

90

100

20

10

-10 -12

0

-20

+15

+10

+5

−5

+5

+0 °C

+0 °C

+0 °C

+0 °C

Characteristic curve

Flo

w t

em

per

atur

e °

 C 

 

Outdoor temperature ° C 

Da

y cor

rection

20

30

40

50

60

70

80

90

100

110

20

10

-10 -12

0

-20

-30

-40

-50

+15

+10

+5

−5

20

30

40

50

60

70

80

90

100

110

20

10

-10 -12

0

-20

+15

+10

−5

20

30

40

50

60

70

80

90

100

20

10

-10 -12

0

-20

-30

-40

-50

+15

+10

+5

−5

20

30

40

50

60

70

80

90

100

20

10

-10 -12

0

-20

+15

+10

+5

−5

+5

+0 °C

+0 °C

+0 °C

+0 °C

Flo

w t

em

per

atur

e ° C 

Characteristic curve

Outdoor temperature ° C

Da

y cor

rection

hc (heating circuit) 2  

settings, Menu 6

dhW settings, Menu 7

hc (heating circuit) 

settings, Menu 5

Содержание 90C-1

Страница 1: ...Please read these instructions in full before using the controller CONTrOLLER Series 90c VRG140 VRB140 VRG130 VRG230 3HG 3H 3G 4G 3F BIV T TM 3MG 4MG 5MG ADAPTER KIT VRG801 ADAPTER KIT VRG900 90C...

Страница 2: ...5 Display and Input 5 Menu Sequence 5 Menu Structure 5 AVAILABLE IN VERSION MENU 90C 1 90C 2 90C 3 1 Measurement 6 90C 1 90C 2 90C 3 2 Statistics 6 90C 1 90C 2 90C 3 3 Operating Times 6 90C 1 90C 2 90...

Страница 3: ...the unit or accessories that are not in perfect condition must be exchanged immediately Use only original spare parts and accessories from the manufacturer Markings made on the unit at the factory mus...

Страница 4: ...th PE Blue Neutral N Brown Phase L Commissioning help Set Up Wizard The first time the controller is turned on and after the language and time are set a query appears as to whether you want to paramet...

Страница 5: ...dditional information Back to previous screen ok confirm selection Confirm confirm setting Out door 0 C Flow 27 C Target fl 27 C Room 21 C Exit main menu 2 Statistics OK 1 Measurements 3 1 Time and da...

Страница 6: ...ck continues to run for about 24 hours if the mains voltage is interrupted and after that has to be reset Menu 3 2 Daylight Saving Automaticly adjust clock f r daylight savings time Menu 3 3 Heating C...

Страница 7: ...in will reset the 14 day reference program and start it at day 1 Menu 4 5 Domestic Hot Water Auto The Domestic Hot Water function is activated according to the schedule in menu 3 5 On The Domestic Hot...

Страница 8: ...re values displayed for example due to cables which are to long or sensors which are not positioned optimally can be compensated for manu ally here The settings can be made for each individual sensor...

Страница 9: ...ce flow temperature is raised or respectiveley lowered ac cording to the percent setting in room sensor If room sensor is set to 0 this function is deactivated Settings range 10 C to 30 C Default 20 C...

Страница 10: ...ings in menu 15 7 3 15 7 5 4 PUMPCONTR HEAT CIRCUIT 1 Connect pump heat circ1 as P1 PUMPCONTR HEAT CIRCUIT 2 Activated when temperature at sensor 3 is lower than specified in menu 6 Connect pump heat...

Страница 11: ...2 Activated when temperature at sensor 3 is lower than specified in menu 6 Connect pump heat circ 2 as P2 Menu 15 7 2 Select Heating circ 2 Settings in menu 6 1 6 6 HEAT SOURCE TEMPERATURE CONTROL By...

Страница 12: ...heat circ1 as P1 SOLAR PUMP CONTROL By floating temperature Connect solar circ pump as P3 Menu 15 7 1 Select Solar Settings in menu 9 1 PUMP CONTROL HEAT CIRCUIT 2 By floating temperature Connect circ...

Страница 13: ...P1 P2 P3 P1 S3 S4 P2 P3 S3 S4 1 2 S3 S4 P1 P2 P3 230 P1 P2 P3 2 1 S4 S3 S3 S4 230 P1 P2 P3 P1 S3 S4 2 1 S3 P1 P2 P3 230 P1 S4 S3 P2 P3 1 S4 2 S3 S4 P1 P2 P3 230 P1 P2 P3 2 1 S4 S3 90C 1 90C 2 90C 3 90...

Страница 14: ...2 S3 S4 S7 230 P1 P2 P3 13 14 P1 S3 2 1 S3 230 P1 P2 P3 P1 P2 P3 1 2 S3 S3 230 P1 P2 P3 P1 P2 P3 S3 S4 S7 1 2 P3 P2 S3 S7 S4 P1 1 2 S4 P2 P1 S3 S7 P3 1 2 230 P1 P2 P3 S3 S7 15 16 S3 S4 S7 230 P1 P2 P...

Страница 15: ...Art nr 9814 98140423 Ritn nr 9226 Utg B 1205 GB...

Отзывы: