Current temperature values with explanations.

Measurements” serves to display the currently mea-

sured temperatures.

The submenus described under 1.1-1.9 are available.
The menu is closed by pressing “esc” or selecting “Exit 

measurements”.

Selecting “Info” leads to a brief help text explaining 

the measurement values.
Selecting “Overview” or “esc” exits the Info mode.

If “Error” appears on the display instead of the measurement value, then there 

may be a defective or incorrect temperature sensor.

What measurement values are displayed depends on the selected program, the connec-

ted sensors and the specific device design.

1.1 outdoor

1.2 floW

1.3 floW 2

1.4 sensor 4

1.5 rooM

1.6 rooM sensor

1.7 rc sWitch

1.8 target floW

1.9 target floW 2

If the cables are too long or the sensors are not placed optimally, the result may be 

small deviations in the measurement values. In this case the display values can be 

compensated for by making entries on the controller. Follow the instructions under 

menu 15.1

Function control of the system with operating hours, etc.

For system data statistics it is essential for the time to be set accurately on the 

controller. Please note that the clock continues to run for about 24 hours if the mains 

voltage is interrupted, and after that has to be reset. Improper operation or an incor-

rect time may result in data being cleared, recorded incorrectly or overwritten.

The manufacturer accepts no liability for the recorded data!

2.1  today (=floW teMPerature during the last 24 hours)

In the graphical overview the characteristics of outdoor-and flow temperature  during 

the last 24 hours is shown. The right button changes the unit of time and the two left 

buttons scroll through the diagram.

2.2  28-days (=floW teMPerature during the last 28 days)

In the graphical overview the characteristics of the outdoor and flow temperature 

during the last 28 days is shown. The right button changes the unit of time (Days) and 

the two left buttons scroll through the diagram.

2.3 outdoor 8760h (1year)

Menu 2.3.1 Current year 

Menu 2.3.2 Previous year  

Menu 2.3.3 2 years ago 
xh: ºC hours. Nr of heating hours when heating is  

required. ie hours with lower outdoor temp than specified. 

xd: ºC days. Nr of heating days when heating is  

required. ie days with lower outdoor temp than specified.

2.4 floW 8760h (1year)

Menu 2.4.1 Current year 

Menu 2.4.2 Previous year  

Menu 2.4.3 2 years ago 
xh: Nr of hours with flow temp higher than specified. 

xd: Nr of days with flow temp higher than specified.

2.5 oPerating hours heat circuit

Menu 2.5.1 Display of operating hours of the circulation pump/aux. heat.  

Menu 2.5.2 The date the measurement started.

2.6 oPerating hours dhW

Menu 2.6.1 Display of operating hours of the DHW 

Menu 2.6.1 The date the measurement started

2.7 oPerating hours heat circuit 2

Menu 2.7.1 Display of operating hours of the circulation pump  

Menu 2.7.2 The date the measurement started.

2.8 oPerating hours heat

Menu 2.8.1 Display of operating hours of the aux. heat. 

Menu 2.8.1 The date the measurement started

2.9 error Messages

Display of the last three errors in the system with indication of date and time.

2.10 reset/clear

Resetting and clearing the individual statistics. Selecting " All statistics clears everyth-

ing except for the error log.

Operating times for heating circuit and hot water setting the clock.

The associated temperature reference values are specified in  

menu 5 ”Settings”!

Menu 3.1 tiMe and date  

This menu is used to set the current time and date.
For proper functioning of the controller and statistics for the system data it is es-

sential for the time to be set accurately on the controller. Please note that the clock 

continues to run for about 24 hours if the mains voltage is interrupted, and after that has 

to be reset.

Menu 3.2 daylight saVing

Automaticly adjust clock för daylight savings time.

Menu 3.3 heating circuit day  

This menu is used to select the daytime mode times for the heating circuit; three time 

periods can be specified for each weekday and copied over to the following days. 

Setting range: Three time ranges for each day of the week 

Default: Mo-Su 6:00-22:00 

Note: See menu 5.6 for the associated temperature settings

Times that are not specified are automatically considered to be nighttime mode. The 

set times are only taken into account in the heating circuit operating mode “Automatic”.
Ex:

Menu 3.4 heating coMfort  

This menu can be used to select a time range for each day of the week in which the 

heating circuit is supplied with an increased comfort temperature, e.g. for quick 

heating in the morning.

Setting range: One time range for each day of the week 

Default: Mo-Su off 

Note: See menu 5.5. for the associated temperature settings.

Ex:

Menu 3.5 hot Water enable

This Menu is activated when Dom. Hot water is selected in menu 15.7.2 

It can be used to select the daytime mode times for the domestic hot water; three 

time periods can be specified for each weekday and copied over to the following days. 

Setting range: Three time ranges for each day of the week 

Default: Mo-Su 6:00-22:00 

Note: See menu 5.4 for the associated temperature settings

Menu 3.6 hot Water  anti-legionella

This Menu is activated when Dom. Hot water is selected in menu 15.7.2 

It can be used to select a time range for each day of the week

Setting range: One time range for each day of the week 

Default: Mo-Su off 

Note: See menu 5.5. for the associated temperature settings.

Operating times for heating circuit and hot water, manual mode 

After an interruption of the mains voltage the controller automatically 

returns to the last operating mode selected!

The controller works with the set operating times and the corresponding different 

reference flow temperature values only in the automatic mode.

Menu 4.1 heat circuit  

Auto =  Automatic/Normal mode using the set times.
Continous Day = The set values for day mode are used.
Continous Night = The set values for night mode are used.
Reference Value = Fixed flow temperature regardless of the outdoor temperature. 

The desired flow temperature has to be set in menu 4.3.
14 day reference value = Specific fixed flow temperatures can be set for the next 14 

days in menu 4.4. After 14 days, the reference temperature of the 14th day is used 

until the operating mode is changed.
Off = Heating circuit is switched off (except Frost protection)

Settings range: Auto, Continous day, Continous night, Reference value, 14 day refe-

rence, Off / Default: Automatic

Menu 4.2 Manual   

In Manual mode the individual relay outputs and the connected consumers can be 

checked for proper functioning and correct assignment. 

The operating mode “Manual” may only be used by specialists for brief 

function tests, e.g. during commissioning!

Function in manual mode: 

The relays and thus the connected consumer are switched on and off by pressing a 

key, with no regard to the current temperatures 

and the parameters which have been set. At the 

same time, the current measurement values of 

temperature sensors are also shown in the display 

for the purposes of function control.

1.1 Outdoor 

 

0ºC

current outdoor temperature

▲        ▼ Overview

1. exit measurements

1.2 Flow 

 0ºC

▲        ▼ 

 Info

1.1 Outdoor 

 

0ºC

              0  6  12 18 24

3.2.1.

 Tue  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.2.1.

 Th  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.2.1.

 Sa  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.2.1.

 Mo  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.2.1.

 We  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.2.1.

 Fr  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.2.1.

 Su  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.3.1. 

Mo  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.3.1. 

We  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.3.1. 

Fr  

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.3.1. 

Tue 

׀   ׀   ׀   ׀   ׀

              0  6  12 18 24

3.3.1. 

Th  

׀   ׀   ׀   ׀   ׀

       1        2       3    

      50%

        

  

On

Manual operation

off

off off

off

off

MeasureMents, Menu 1

statistics, Menu 2

tiMes, Menu 3

oPerating Mode, Menu 4

Содержание 90C-1

Страница 1: ...Please read these instructions in full before using the controller CONTrOLLER Series 90c VRG140 VRB140 VRG130 VRG230 3HG 3H 3G 4G 3F BIV T TM 3MG 4MG 5MG ADAPTER KIT VRG801 ADAPTER KIT VRG900 90C...

Страница 2: ...5 Display and Input 5 Menu Sequence 5 Menu Structure 5 AVAILABLE IN VERSION MENU 90C 1 90C 2 90C 3 1 Measurement 6 90C 1 90C 2 90C 3 2 Statistics 6 90C 1 90C 2 90C 3 3 Operating Times 6 90C 1 90C 2 90...

Страница 3: ...the unit or accessories that are not in perfect condition must be exchanged immediately Use only original spare parts and accessories from the manufacturer Markings made on the unit at the factory mus...

Страница 4: ...th PE Blue Neutral N Brown Phase L Commissioning help Set Up Wizard The first time the controller is turned on and after the language and time are set a query appears as to whether you want to paramet...

Страница 5: ...dditional information Back to previous screen ok confirm selection Confirm confirm setting Out door 0 C Flow 27 C Target fl 27 C Room 21 C Exit main menu 2 Statistics OK 1 Measurements 3 1 Time and da...

Страница 6: ...ck continues to run for about 24 hours if the mains voltage is interrupted and after that has to be reset Menu 3 2 Daylight Saving Automaticly adjust clock f r daylight savings time Menu 3 3 Heating C...

Страница 7: ...in will reset the 14 day reference program and start it at day 1 Menu 4 5 Domestic Hot Water Auto The Domestic Hot Water function is activated according to the schedule in menu 3 5 On The Domestic Hot...

Страница 8: ...re values displayed for example due to cables which are to long or sensors which are not positioned optimally can be compensated for manu ally here The settings can be made for each individual sensor...

Страница 9: ...ce flow temperature is raised or respectiveley lowered ac cording to the percent setting in room sensor If room sensor is set to 0 this function is deactivated Settings range 10 C to 30 C Default 20 C...

Страница 10: ...ings in menu 15 7 3 15 7 5 4 PUMPCONTR HEAT CIRCUIT 1 Connect pump heat circ1 as P1 PUMPCONTR HEAT CIRCUIT 2 Activated when temperature at sensor 3 is lower than specified in menu 6 Connect pump heat...

Страница 11: ...2 Activated when temperature at sensor 3 is lower than specified in menu 6 Connect pump heat circ 2 as P2 Menu 15 7 2 Select Heating circ 2 Settings in menu 6 1 6 6 HEAT SOURCE TEMPERATURE CONTROL By...

Страница 12: ...heat circ1 as P1 SOLAR PUMP CONTROL By floating temperature Connect solar circ pump as P3 Menu 15 7 1 Select Solar Settings in menu 9 1 PUMP CONTROL HEAT CIRCUIT 2 By floating temperature Connect circ...

Страница 13: ...P1 P2 P3 P1 S3 S4 P2 P3 S3 S4 1 2 S3 S4 P1 P2 P3 230 P1 P2 P3 2 1 S4 S3 S3 S4 230 P1 P2 P3 P1 S3 S4 2 1 S3 P1 P2 P3 230 P1 S4 S3 P2 P3 1 S4 2 S3 S4 P1 P2 P3 230 P1 P2 P3 2 1 S4 S3 90C 1 90C 2 90C 3 90...

Страница 14: ...2 S3 S4 S7 230 P1 P2 P3 13 14 P1 S3 2 1 S3 230 P1 P2 P3 P1 P2 P3 1 2 S3 S3 230 P1 P2 P3 P1 P2 P3 S3 S4 S7 1 2 P3 P2 S3 S7 S4 P1 1 2 S4 P2 P1 S3 S7 P3 1 2 230 P1 P2 P3 S3 S7 15 16 S3 S4 S7 230 P1 P2 P...

Страница 15: ...Art nr 9814 98140423 Ritn nr 9226 Utg B 1205 GB...

Отзывы: