Note! All applicationexamples are overall idea sketches, and do not claim to be complete. Always also take locally laws and regulations into consideration.
The controller does not replace safety devices under any circumstances.
Depending on the specific application, additional system components and safety components may be mandatory, such as check valves, non-return valves, safety temperature limiters, scalding
protectors, etc., and must therefore be provided.
hydronic Variants
aPPl.
aVailable
for
Version
function 90c
electrical
connection
settting
1
PuMP control heat circuit 1
Connect pump heat circ1 as P1
Menu 15.7.1
Select: Circulation pump
2
auxiliary heat control
Activated by mixer position.
Connect aux heat as P1 (90C-1)
Connect aux heat as P3 (90C-2,90C-3)
Menu 15.7.1
Select: Position
Settings in menu 15.7.3 – 15.7.5
3
PuMPcontr. heat circuit 1
Connect pump heat circ1 as P1
auxiliary heat control
Activated by mixer position
Connect aux heat as P3
Menu 15.7.1
Select: Position
Settings in menu 15.7.3 – 15.7.5
4
PuMPcontr. heat circuit 1
Connect pump heat circ1 as P1
PuMPcontr. heat circuit 2
Activated when temperature at sensor 3 is
lower than specified in menu 6.
Connect pump heat circ 2 as P2
Connect sensor as sensor 3 in sensor
box 2
Menu 15.7.2
Select: Heating circ 2
Settings in menu 6.1-6.6
5
PuMPcontr. heat circuit 1
Connect pump heat circ1 as P1
auxiliary heat control
Activated by mixer position
Connect aux heat as P3
Menu 15.7.1
Select: Position
Settings in menu 15.7.3 – 15.7.5
PuMPcontr. heat circuit 2
Activated when temperature at sensor 3 is
lower than specified in menu 6.
Connect pump heat circ 2 as P2
Connect sensor as sensor 3 in sensor
box 2
Menu 15.7.2
Select: Heating circ 2
Settings in menu 6.1-6.6
6
PuMP control heat circuit 1
Connect pump heat circ1 as P1
PuMPcontr. heat circuit 2
Activated when temperature at sensor 3 is
lower than specified in menu 6.
Connect pump heat circ 2 as P2
Menu 15.7.2
Select: Heating circ 2
Settings in menu 6.1-6.6
heat source teMPerature control
With heat circuit as reference temp.
Connect boiler as P3
Menu 15.7.1
Select: Temperature
Settings in menu 5.7-5.8
Connect sensor as sensor 3+4 in
sensor box 2
90c-