background image

 35

 Page 32

Refrigerant piping

Connection

2. 

Tighten the flare nut as tightly as possible by 

hand.

3. 

Using a spanner, grip the nut on the unit 

tubing.

4. 

While firmly gripping the nut on the unit 

tubing, use a torque wrench to tighten the 

flare nut according to the torque values in the 

Torque Requirements 

table below. Loosen 

the flaring nut slightly, then tighten again.

Instructions for Connecting Piping to Outdoor Unit

USE SPANNER TO GRIP MAIN 
BODY OF VALVE

Torque from tightening the flare nut can snap 

off other parts of valve. 

TORQUE REQUIREMENTS

Outer Diameter of Pipe
 (mm)

Tightening Torque
 (N•m)

Flare dimension(B)
 (mm)

Flare shape
 

Ø 6.35 (Ø 0.25”)

8.4~8.7 (0.33~0.34”)

13.2~13.5 (0.52~0.53”)

16.2~16.5 (0.64~0.65”)

19.2~19.7 (0.76~0.78”)

23.2~23.7 (0.91~0.93”)

18~20(180~200kgf.cm)

32~39(320~390kgf.cm)

49~59(490~590kgf.cm)

57~71(570~710kgf.cm)

67~101(670~1010kgf.cm)

Ø 9.52 (Ø 0.375”)

Ø 12.7 (Ø 0.5”)

Ø 16 (Ø 0.63”)

Ø 19 ( Ø 0.75”)

1. 

Unscrew the cover from the packed valve on 

the side of the outdoor unit.

2. 

Remove protective caps from ends of valves.

3. 

Align flared pipe end with each valve, and 

tighten the flare nut as tightly as possible by 

hand.

4. 

Using a spanner, grip the body of the valve. 

Do not grip the nut that seals the service 

valve. 

5. 

While firmly gripping the body of the valve, 

use a torque wrench to tighten the flare nut 

according to the correct torque values.

6. 

Loosen the flaring nut slightly, then tighten 

again.

7. 

Repeat Steps 3 to 6 for the remaining pipe.

 DO NOT USE EXCESSIVE TORQUE

Excessive force can break the nut or damage the refrigerant piping. You must not exceed  

torque requirements shown in the table above.

Valve cover

R0.4~0. 8

45

°±

2

90

°      

±

4

B

 Page 33

Air Evacuation

 

Preparations and Precautions

Air and foreign matter in the refrigerant circuit can 
cause abnormal rises in pressure, which can damage 
the air conditioner, reduce its efficiency, and cause
injury. Use a vacuum pump and manifold gauge to 
evacuate the refrigerant circuit, removing any 
non-condensable gas and moisture from the system.      

Evacuation should be performed upon initial 
installation and when unit is relocated. 

BEFORE PERFORMING EVACUATION

  

Check to make sure the connective pipes

between the indoor and outdoor units 

are connected properly . 

  

Check to make sure all wiring is connected 

properly.

Evacuation Instructions

Manifold Gauge

Compound 

gauge

-76cmHg

Low pressure 

valve

High pressure

valve

Pressure hose / 

Charge hose

Charge hose

V

acuum

pump

Pressure gauge

Low pressure valve

1.

 

Connect the charge hose of the manifold 

gauge to service port on the outdoor unit’s 

low pressure valve. 

Connect another charge hose from the 

manifold gauge to the vacuum pump. 

Open the Low Pressure side of the manifold 
gauge. Keep the High Pressure side closed. 
Turn on the vacuum pump to evacuate the 
system.
Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG
(-10  Pa).    

  

2.

 

3.

 

4.

 

5.

5

6.

 

Close the Low Pressure side of the manifold 

gauge, and turn off the vacuum pump.

7.

 

Wait for 5 minutes, then check that there 

has been no change in system pressure.

8.

 

If there is a change in system pressure, refer 

to Gas Leak Check section for information 

on how to check for leaks. If there is no 

change in system pressure, unscrew the cap 

from the packed valve (high pressure valve).

9.

 

Insert hexagonal wrench into the packed valve 

(high pressure valve) and open the valve by 

turning the wrench in a 1/4 counterclockwise 

turn. Listen for gas to exit the system, then 

close the valve after 5 seconds.

10. 

Watch the Pressure Gauge for one minute 

to make sure that there is no change in 

pressure. The Pressure Gauge should read 

slightly higher than atmospheric pressure.

Flare nut

Cap

valve body

valve stem

11.

 

Remove the charge hose from the service port.

12.  

Using hexagonal wrench, fully open both the 

high pressure and low pressure valves.

13.  

Tighten valve caps on all three valves (service 

port, high pressure, low pressure) by hand. 

You may tighten it further using a torque 

wrench if needed.

 OPEN VALVE STEMS GENTLY

 

When opening valve stems, turn the hexagonal 

wrench until it hits against the stopper. Do not 

try to force the valve to open further.

Air Evacuation

Содержание ESAC25RC

Страница 1: ...rManual Exactly what you need Model Code s ESAC25RC ESAC35RC ESAC50RC Online esatto house Product 2 5kW Split System Air Conditioner 3 5kW Split System Air Conditioner 5 0kW Split System Air Condition...

Страница 2: ...mportantly taking care of the appliance our Support Team are here to help You can use our online Support Centre at anytime by visiting http support residentiagroup com au Or you can contact us via pho...

Страница 3: ...essories Page 20 Installation Summary Indoor Page 21 Unit Parts Page 22 Indoor Unit Installation Page 28 Outdoor Unit Installation Page 32 Refrigerant Piping Connection Page 35 Air Evacuation Page 37...

Страница 4: ...4 Safety This page is intentionally left blank...

Страница 5: ...ises like a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects in...

Страница 6: ...share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection device which ha...

Страница 7: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Страница 8: ...chanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be re fabricated IEC Standard Requirements European Disposal Guidelines...

Страница 9: ...when TIMER ON is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned on for 3 seconds when TIMER OFF is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned off when defrosting...

Страница 10: ...TURBO or SILENCE features is turned off when defrosting for cooling heating units when unit is self cleaning some units when fresh feature is turned on some units when ECO feature is activated some un...

Страница 11: ...22 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Страница 12: ...settings to stay comfortable This function can only be activated via remote control And the Sleep function is not available in FAN or DRY mode Press the SLEEP button when you are ready to go to sleep...

Страница 13: ...gers in or near the blower and suction side of the unit The high speed fan inside the unit may cause injury Fig B Fig A Setting Angle of Air Flow Setting horizontal angle of air flow To operate your u...

Страница 14: ...o be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter lift it up then pull it towards yourself 3...

Страница 15: ...e If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect th...

Страница 16: ...s Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may...

Страница 17: ...t customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following p...

Страница 18: ...Poor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 19: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote c...

Страница 20: ...Mounting Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in...

Страница 21: ...e requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Страница 22: ...direct sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipi...

Страница 23: ...ure to avoid wires plumbing and other sensitive components Type A Type B 101mm 4in 179mm 7 05in 136mm 5 35in 37mm 1 45in 290mm 11 4in 49mm 1 95in Right rear wall hole 65mm 2 5in Indoor unit outline 72...

Страница 24: ...k out Panel CAUTION Be extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By...

Страница 25: ...rmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire Do not let wires touch or rest against refrigerant tubing the compressor or any moving...

Страница 26: ...l on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can le...

Страница 27: ...pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto th...

Страница 28: ...wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or s...

Страница 29: ...ubber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain...

Страница 30: ...ce a nut on the end of each expansion bolt 4 Hammer expansion bolts into the pre drilled holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bol...

Страница 31: ...clamp down tightly 7 Insulate unused wires with PVC electrical tape Arrange them so that they do not touch any electrical or metal parts 8 Replace the wire cover on the side of the unit and screw it i...

Страница 32: ...er than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrigeration cycle This can cau...

Страница 33: ...rrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve...

Страница 34: ...7 0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the p...

Страница 35: ...m for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Страница 36: ...00Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump L...

Страница 37: ...Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using...

Страница 38: ...pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe con...

Страница 39: ...specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service w...

Страница 40: ...details of your purchase below and staple your receipt on the opposite page Your serial number can be found on the Rating Label which is applied to your unit STORE DETAILS STORE NAME ADDRESS TELEPHON...

Страница 41: ...41 Attach your receipt to this page...

Страница 42: ...during the Warranty Period g Warranty Period means i where the Appliance is used for personal domestic or household use i e normal single family use as set out in the instruction manual the Appliance...

Страница 43: ...g from your purchase use or non use of the Appliance 10 For Appliances and services provided by Residentia Group in Australia the Appliances come with a guarantee by Residentia Group that cannot be ex...

Страница 44: ...This page is intentionally left blank Appliances Exactly what you need A RESIDENTIA GROUP INITIATIVE...

Отзывы: