Outdoor Unit 

  Installation

 Page 26 

Installation

 

 

ev

o

ba 

)

ni

42

mc

06

60cm (24in) 

on righ

t

30cm (12in) 

on left

200cm (79in) 

in fron

t

30cm (12in) 

from back wall

Installation Instructions – Outdoor unit 

Step 1: Select installation location

Before installing the outdoor unit, you must 
choose an appropriate location. The following are 
standards that will help you choose an appropriate
location for the unit.  

Proper installation locations meet the 

following standards:

 

Meets all spatial requirements shown in 

Installation Space Requirements above.

 

Good air circulation and ventilation

 

Firm and solid—the location can support the 

unit and will not vibrate

 

Noise from the unit will not disturb others 

Install the unit by following local codes and 
regulations , there may be differ slightly 
between different regions.  

SPECIAL CONSIDERATIONS FOR EXTREME 

WEATHER
If the unit is exposed to heavy wind:

Install unit so that air outlet fan is at a 90° 

angle to the direction of the wind. If needed, 

build a barrier in front of the unit to protect it 

from extremely heavy winds.

See Figures below

.

 

Strong
 wind

Strong wind

Strong wind

If the unit is frequently exposed to heavy 

rain or snow:

Build a shelter above the unit to protect 

it from the rain or snow.  Be careful not to 

obstruct air flow around the unit.

If the unit is frequently exposed to salty air 

(seaside): 

Use outdoor unit that is specially designed to 

resist corrosion.

Wind Baffle

 

Protected from prolonged periods of direct 

sunlight or rain

 

DO NOT

 install unit in the following locations:

 

Near an obstacle that will block air inlets 

and outlets

 

Near a public street, crowded areas, or 

where noise from the unit will disturb others 

 

Near animals or plants that will be harmed 

by hot air discharge

 

Near any source of combustible gas

 

In a location that is exposed to large 

amounts of dust

 

In a location exposed to a excessive amounts 

of salty air

 

Where snowfall is anticipated, raise the 
unit above the base pad to prevent ice 
buildup and coil damage. Mount the unit 
high enough to be above the average 
accumulated area snowfall. The minimum 
height must be 18 inches

 

Outdoor Unit Installation

 Page 27

Outdoor Unit 

  Installation

Step 2: Install drain joint(Heat pump unit only)

Before bolting the outdoor unit in place, you must  

install the drain joint at the bottom of the unit.

Note  that there are two different types of drain 

joints depending on the type of outdoor unit. 

If the drain joint comes with a rubber seal

(see 

Fig.  A 

), do the following:

1.

 Fit the rubber seal on the end of the drain joint 

that will connect to the outdoor unit.

2.

 

Insert the drain joint into the hole in the base 

pan of the unit.

3.

 Rotate the drain joint 90° until it clicks in place 

facing the front of the unit.

4.

 Connect a drain hose extension (not included) 

to the drain joint to redirect water from the 

unit during heating mode.

If the drain joint doesn’t come with a rubber 

seal 

(see 

Fig. B 

), do the following: 

 

1.

 Insert the drain joint into the hole in the base 

pan of the unit. The drain joint will click in 

place.

2.

 Connect a drain hose extension (not included) 

to the drain joint to redirect water from the 

unit during heating mode.

Seal

Drain joint

(A)

(B)

Base pan hole of

outdoor unit

Seal 

 IN COLD CLIMATES 

In cold climates, make sure that the drain hose 

is as vertical as possible to ensure swift water 

drainage. If water drains too slowly, it can 

freeze in the hose and flood  the unit.

The outdoor unit can be anchored to the 
ground or to a wall-mounted bracket with 
bolt(M10). Prepare the installation base of the 
unit according to the dimensions below. 

A

W

B

D

Air inlet

Air outlet

Air inlet

W

H

Step 3: Anchor outdoor unit

UNIT MOUNTING DIMENSIONS

The following is a list of different outdoor 
unit sizes and the distance between their 
mounting feet. Prepare the installation base 
of the unit according to the dimensions 
below. 

Содержание ESAC25RC

Страница 1: ...rManual Exactly what you need Model Code s ESAC25RC ESAC35RC ESAC50RC Online esatto house Product 2 5kW Split System Air Conditioner 3 5kW Split System Air Conditioner 5 0kW Split System Air Condition...

Страница 2: ...mportantly taking care of the appliance our Support Team are here to help You can use our online Support Centre at anytime by visiting http support residentiagroup com au Or you can contact us via pho...

Страница 3: ...essories Page 20 Installation Summary Indoor Page 21 Unit Parts Page 22 Indoor Unit Installation Page 28 Outdoor Unit Installation Page 32 Refrigerant Piping Connection Page 35 Air Evacuation Page 37...

Страница 4: ...4 Safety This page is intentionally left blank...

Страница 5: ...ises like a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects in...

Страница 6: ...share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection device which ha...

Страница 7: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Страница 8: ...chanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be re fabricated IEC Standard Requirements European Disposal Guidelines...

Страница 9: ...when TIMER ON is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned on for 3 seconds when TIMER OFF is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned off when defrosting...

Страница 10: ...TURBO or SILENCE features is turned off when defrosting for cooling heating units when unit is self cleaning some units when fresh feature is turned on some units when ECO feature is activated some un...

Страница 11: ...22 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Страница 12: ...settings to stay comfortable This function can only be activated via remote control And the Sleep function is not available in FAN or DRY mode Press the SLEEP button when you are ready to go to sleep...

Страница 13: ...gers in or near the blower and suction side of the unit The high speed fan inside the unit may cause injury Fig B Fig A Setting Angle of Air Flow Setting horizontal angle of air flow To operate your u...

Страница 14: ...o be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter lift it up then pull it towards yourself 3...

Страница 15: ...e If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect th...

Страница 16: ...s Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may...

Страница 17: ...t customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following p...

Страница 18: ...Poor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 19: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote c...

Страница 20: ...Mounting Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in...

Страница 21: ...e requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Страница 22: ...direct sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipi...

Страница 23: ...ure to avoid wires plumbing and other sensitive components Type A Type B 101mm 4in 179mm 7 05in 136mm 5 35in 37mm 1 45in 290mm 11 4in 49mm 1 95in Right rear wall hole 65mm 2 5in Indoor unit outline 72...

Страница 24: ...k out Panel CAUTION Be extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By...

Страница 25: ...rmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire Do not let wires touch or rest against refrigerant tubing the compressor or any moving...

Страница 26: ...l on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can le...

Страница 27: ...pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto th...

Страница 28: ...wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or s...

Страница 29: ...ubber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain...

Страница 30: ...ce a nut on the end of each expansion bolt 4 Hammer expansion bolts into the pre drilled holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bol...

Страница 31: ...clamp down tightly 7 Insulate unused wires with PVC electrical tape Arrange them so that they do not touch any electrical or metal parts 8 Replace the wire cover on the side of the unit and screw it i...

Страница 32: ...er than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrigeration cycle This can cau...

Страница 33: ...rrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve...

Страница 34: ...7 0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the p...

Страница 35: ...m for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Страница 36: ...00Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump L...

Страница 37: ...Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using...

Страница 38: ...pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe con...

Страница 39: ...specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service w...

Страница 40: ...details of your purchase below and staple your receipt on the opposite page Your serial number can be found on the Rating Label which is applied to your unit STORE DETAILS STORE NAME ADDRESS TELEPHON...

Страница 41: ...41 Attach your receipt to this page...

Страница 42: ...during the Warranty Period g Warranty Period means i where the Appliance is used for personal domestic or household use i e normal single family use as set out in the instruction manual the Appliance...

Страница 43: ...g from your purchase use or non use of the Appliance 10 For Appliances and services provided by Residentia Group in Australia the Appliances come with a guarantee by Residentia Group that cannot be ex...

Страница 44: ...This page is intentionally left blank Appliances Exactly what you need A RESIDENTIA GROUP INITIATIVE...

Отзывы: