background image

 33

 Page 30

Note on Pipe Length

The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal 

efficiency is tested on units with a pipe length of 5 meters (16.5ft). A  minimum pipe run of 3 metres is 
required to minimise vibration & excessive noise.
In special tropical area, for the R290 refrigerant models, no refrigerant can be added and the maximum
length of refrigerant pipe should not exceed 10 meters(32.8ft).

Connection Instructions –  Refrigerant Piping

Step 1: Cut pipes

When preparing refrigerant pipes, take extra 
care to cut and flare them properly. This will 
ensure efficient operation and minimize the 
need for future maintenance.   

 

1. Measure the distance between the indoor 
    and outdoor units. 

Refer to the table below for specifications on the maximum length and drop height of piping.

 

When connecting refrigerant piping, 

do not

 let substances or gases other than the specified 

refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, 

and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury. 

2.

 

Using a pipe cutter, cut the pipe a little longer 

than the measured distance.

3.

 

Make sure that the pipe is cut at a perfect 90° 

angle. 

Oblique Rough Warped

90°

 

DO NOT DEFORM PIPE

 

 WHILE CUTTING

Be extra careful not to damage, dent, or 

deform the pipe while cutting. This will 

drastically reduce the heating efficiency 

 of the unit.

Maximum Length and Drop Height of Refrigerant Piping per Unit Model

Model

Capacity (BTU/h)

Max. Length (m)

Max. Drop Height (m)

R410A,R32 Inverter Split Air 

Conditioner

R22 Fixed-speed

Split Air Conditioner

R410A, R32 Fixed-speed

Split Air Conditioner

< 15,000

< 18,000

25 (82ft)

10 (33ft)

10 (33ft)

5 (16ft)

 15,000 and < 24,000

30 (98.5ft)

20 (66ft)

20 (66ft)

 24,000 and < 36,000

50 (164ft)

25 (82ft)

 21,000 and < 35,000

10(33ft)

 18,000 and < 21,000

 18,000 and < 36,000

15 (49ft)

8(26ft)

8(26ft)

< 18,000

20 (66ft)
25 (82ft)

10(33ft)

Refrigerant piping

Connection

Refrigerant Piping Connection 

 Page 31

 

6. 

Place flaring tool onto the form.

7. 

Turn the handle of the flaring tool clockwise 

until the pipe is fully flared.

8. 

Remove the flaring tool and flare form, then 

inspect the end of the pipe for cracks and 

even flaring.

Step 4: Connect pipes

When connecting refrigerant pipes, be careful 

not to use excessive torque or to deform the 

piping in any way. You should first connect the 

low-pressure pipe, then the high-pressure pipe.

MINIMUM BEND RADIUS

When bending connective refrigerant piping, 

the minimum bending radius is 10cm. 

≥10cm (4in)

Radius

Instructions for Connecting Piping to 

Indoor Unit

1. 

Align the center of the two pipes that you will 

connect. 

Indoor unit tubing

Flare nut

Pipe

Max.

Step 2: Remove burrs

Burrs can affect the air-tight seal of refrigerant 

piping connection. They must be completely 

removed.

1. 

Hold the pipe at a downward angle to prevent 

burrs from falling into the pipe.

2. 

Using a reamer or deburring tool, remove all 

burrs from the cut section of the pipe.

Pipe

Reamer

Point down

Step 3: Flare pipe ends

Proper flaring is essential to achieve an airtight 

seal.

1. 

After removing burrs from cut pipe, seal 

the ends with PVC tape to prevent foreign 

materials from entering the pipe. 

2. 

Sheath the pipe with insulating material.

3. 

Place flare nuts on both ends of pipe. Make 

sure they are facing in the right direction, 

because you can’t put them on or change 

their direction after flaring. 

Flare nut

Copper pipe

4. 

Remove PVC tape from ends of pipe when 

ready to perform flaring work.

5. 

Clamp flare form on the end of the pipe. 

The end of the pipe must extend beyond the 

edge of the flare form in accordance with the 

dimensions shown in the table below.

PIPING EXTENSION BEYOND FLARE FORM

Outer Diameter of 

Pipe (mm)

A (mm)

Min.

Max.

Ø 6.35 (Ø 0.25”)

0.7 (0.0275”) 1.3 (0.05”)

Ø 9.52 (Ø 0.375”)

1.0 (0.04”)

1.6 (0.063”)

Ø12.7 ( Ø 0.5”)

1.0 (0.04”)

1.8 (0.07”)

Ø 16 ( Ø 0.63”)
Ø 19 ( Ø 0.75”)

2.0 (0.078”)

2.2 (0.086”)

2.0 (0.078”)

2.4 (0.094”)

Flare form

Pipe

A

Refrigerant piping

Connection

Содержание ESAC25RC

Страница 1: ...rManual Exactly what you need Model Code s ESAC25RC ESAC35RC ESAC50RC Online esatto house Product 2 5kW Split System Air Conditioner 3 5kW Split System Air Conditioner 5 0kW Split System Air Condition...

Страница 2: ...mportantly taking care of the appliance our Support Team are here to help You can use our online Support Centre at anytime by visiting http support residentiagroup com au Or you can contact us via pho...

Страница 3: ...essories Page 20 Installation Summary Indoor Page 21 Unit Parts Page 22 Indoor Unit Installation Page 28 Outdoor Unit Installation Page 32 Refrigerant Piping Connection Page 35 Air Evacuation Page 37...

Страница 4: ...4 Safety This page is intentionally left blank...

Страница 5: ...ises like a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects in...

Страница 6: ...share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection device which ha...

Страница 7: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Страница 8: ...chanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be re fabricated IEC Standard Requirements European Disposal Guidelines...

Страница 9: ...when TIMER ON is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned on for 3 seconds when TIMER OFF is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned off when defrosting...

Страница 10: ...TURBO or SILENCE features is turned off when defrosting for cooling heating units when unit is self cleaning some units when fresh feature is turned on some units when ECO feature is activated some un...

Страница 11: ...22 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Страница 12: ...settings to stay comfortable This function can only be activated via remote control And the Sleep function is not available in FAN or DRY mode Press the SLEEP button when you are ready to go to sleep...

Страница 13: ...gers in or near the blower and suction side of the unit The high speed fan inside the unit may cause injury Fig B Fig A Setting Angle of Air Flow Setting horizontal angle of air flow To operate your u...

Страница 14: ...o be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter lift it up then pull it towards yourself 3...

Страница 15: ...e If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect th...

Страница 16: ...s Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may...

Страница 17: ...t customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following p...

Страница 18: ...Poor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 19: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote c...

Страница 20: ...Mounting Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in...

Страница 21: ...e requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Страница 22: ...direct sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipi...

Страница 23: ...ure to avoid wires plumbing and other sensitive components Type A Type B 101mm 4in 179mm 7 05in 136mm 5 35in 37mm 1 45in 290mm 11 4in 49mm 1 95in Right rear wall hole 65mm 2 5in Indoor unit outline 72...

Страница 24: ...k out Panel CAUTION Be extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By...

Страница 25: ...rmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire Do not let wires touch or rest against refrigerant tubing the compressor or any moving...

Страница 26: ...l on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can le...

Страница 27: ...pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto th...

Страница 28: ...wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or s...

Страница 29: ...ubber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain...

Страница 30: ...ce a nut on the end of each expansion bolt 4 Hammer expansion bolts into the pre drilled holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bol...

Страница 31: ...clamp down tightly 7 Insulate unused wires with PVC electrical tape Arrange them so that they do not touch any electrical or metal parts 8 Replace the wire cover on the side of the unit and screw it i...

Страница 32: ...er than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrigeration cycle This can cau...

Страница 33: ...rrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve...

Страница 34: ...7 0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the p...

Страница 35: ...m for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Страница 36: ...00Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump L...

Страница 37: ...Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using...

Страница 38: ...pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe con...

Страница 39: ...specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service w...

Страница 40: ...details of your purchase below and staple your receipt on the opposite page Your serial number can be found on the Rating Label which is applied to your unit STORE DETAILS STORE NAME ADDRESS TELEPHON...

Страница 41: ...41 Attach your receipt to this page...

Страница 42: ...during the Warranty Period g Warranty Period means i where the Appliance is used for personal domestic or household use i e normal single family use as set out in the instruction manual the Appliance...

Страница 43: ...g from your purchase use or non use of the Appliance 10 For Appliances and services provided by Residentia Group in Australia the Appliances come with a guarantee by Residentia Group that cannot be ex...

Страница 44: ...This page is intentionally left blank Appliances Exactly what you need A RESIDENTIA GROUP INITIATIVE...

Отзывы: