oubleshooting

Problem

Possible Causes

Solution

The unit is not
working 

Power failure

Wait for the power to be restored 

The power is turned off

Turn on the power

The fuse is burned out

Replace the fuse

Remote control batteries are dead  Replace batteries

The Unit’s 3-minute protection
has been activated 

Wait three minutes after restarting 
the unit 

Timer is activated

Turn timer off

The unit starts and
stops frequently 

There’s too much or too little
refrigerant in the system 

Check for leaks and recharge the 
system with refrigerant.  

Incompressible gas or moisture 
has entered the system.  

Evacuate and recharge the system 
with refrigerant 

The compressor is broken

Replace the compressor

The voltage is too high or
too low 

Install a manostat to regulate the 
voltage 

Poor heating
performance 

The outdoor temperature is
extremely low 

Use auxiliary heating device 

Cold air is entering through
doors and windows 

Make sure that all doors  and 
windows are closed during use    

Low refrigerant due to leak or
long-term use 

Check for leaks, re-seal if necessary 
and top off refrigerant  

Indicator lamps
continue flashing 

The unit may stop operation or continue to run safely. If the indicator 
lamps continue to flash or error codes appear, wait for about 10 
minutes. The problem may resolve itself. 
If not, disconnect the power, then connect it again. Turn the unit on. 
If the problem persists, disconnect the power and contact your nearest 
customer service center.  

Error code appears and
begins with the letters
as the following in the
window display of 
indoor unit:
  E(x), P(x), F(x)
  EH(xx), EL(xx), EC(xx)
  PH(xx), PL(xx), PC(xx)

• 

• 

NOTE:

 If your problem persists after performing the checks and diagnostics above, 
 turn off your unit immediately and contact an authorized service center.  

 

 

 Page 17 

Accessories

The air conditioning system comes with the following accessories. Use all of the installation parts 
and accessories to install the air conditioner. Improper installation may result in water leakage, 
electrical shock and fire, or cause the equipment to fail. The items are not included
with the air conditioner must be purchased separately. 

Magnetic ring and belt

 

Varies by model

1   2   3   

(if supplied ,please refer to 

the wiring diagram to install 

it on the connective cable. )

 Pass the belt through

 the hole of the Magnetic 

 ring  to fix it on the cable  

Name

Shape

Quantity(PC)

                
(Need to be installed on 
the back of main air filter 
by the authorized 
technician while installing
the machine)

Mounting plate
fixing screw 

Remote controller 

Fixing screw for 
remote controller 
holder(optional) 

Remote controller 
holder(optional)

          Drain joint
     (for cooling & 
      heating models)

           Seal
     (for cooling & 
      heating models)

Mounting plate

Manual

Parts you must purc hase 
separately. Consult the dealer
about the proper pipe size of
the unit you purchased.

  

Connecting pipe 
assembly

Liquid side

Gas side

Φ

6.35( 1/4 i n)

Φ

9.52( 3/8in)

Φ

9.52( 3/8in)

Φ

12.7( 1/2in)

Φ

 16( 5/8in) 

Φ

 19( 3/4in) 

Accessories

2-3

1

1

1

 Anchor

1

2

1

2

Battery

Small Filter

    1~2

(depending

on models)

    5~8

(depending

on models)

    5~8

(depending

on models)

Name of Accessories

Name of Accessories

Q’ty(pc)

Shape

Q’ty(pc)

Shape

Содержание ESAC25RC

Страница 1: ...rManual Exactly what you need Model Code s ESAC25RC ESAC35RC ESAC50RC Online esatto house Product 2 5kW Split System Air Conditioner 3 5kW Split System Air Conditioner 5 0kW Split System Air Condition...

Страница 2: ...mportantly taking care of the appliance our Support Team are here to help You can use our online Support Centre at anytime by visiting http support residentiagroup com au Or you can contact us via pho...

Страница 3: ...essories Page 20 Installation Summary Indoor Page 21 Unit Parts Page 22 Indoor Unit Installation Page 28 Outdoor Unit Installation Page 32 Refrigerant Piping Connection Page 35 Air Evacuation Page 37...

Страница 4: ...4 Safety This page is intentionally left blank...

Страница 5: ...ises like a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects in...

Страница 6: ...share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection device which ha...

Страница 7: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Страница 8: ...chanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be re fabricated IEC Standard Requirements European Disposal Guidelines...

Страница 9: ...when TIMER ON is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned on for 3 seconds when TIMER OFF is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned off when defrosting...

Страница 10: ...TURBO or SILENCE features is turned off when defrosting for cooling heating units when unit is self cleaning some units when fresh feature is turned on some units when ECO feature is activated some un...

Страница 11: ...22 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Страница 12: ...settings to stay comfortable This function can only be activated via remote control And the Sleep function is not available in FAN or DRY mode Press the SLEEP button when you are ready to go to sleep...

Страница 13: ...gers in or near the blower and suction side of the unit The high speed fan inside the unit may cause injury Fig B Fig A Setting Angle of Air Flow Setting horizontal angle of air flow To operate your u...

Страница 14: ...o be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter lift it up then pull it towards yourself 3...

Страница 15: ...e If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect th...

Страница 16: ...s Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may...

Страница 17: ...t customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following p...

Страница 18: ...Poor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 19: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote c...

Страница 20: ...Mounting Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in...

Страница 21: ...e requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Страница 22: ...direct sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipi...

Страница 23: ...ure to avoid wires plumbing and other sensitive components Type A Type B 101mm 4in 179mm 7 05in 136mm 5 35in 37mm 1 45in 290mm 11 4in 49mm 1 95in Right rear wall hole 65mm 2 5in Indoor unit outline 72...

Страница 24: ...k out Panel CAUTION Be extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By...

Страница 25: ...rmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire Do not let wires touch or rest against refrigerant tubing the compressor or any moving...

Страница 26: ...l on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can le...

Страница 27: ...pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto th...

Страница 28: ...wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or s...

Страница 29: ...ubber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain...

Страница 30: ...ce a nut on the end of each expansion bolt 4 Hammer expansion bolts into the pre drilled holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bol...

Страница 31: ...clamp down tightly 7 Insulate unused wires with PVC electrical tape Arrange them so that they do not touch any electrical or metal parts 8 Replace the wire cover on the side of the unit and screw it i...

Страница 32: ...er than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrigeration cycle This can cau...

Страница 33: ...rrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve...

Страница 34: ...7 0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the p...

Страница 35: ...m for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Страница 36: ...00Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump L...

Страница 37: ...Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using...

Страница 38: ...pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe con...

Страница 39: ...specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service w...

Страница 40: ...details of your purchase below and staple your receipt on the opposite page Your serial number can be found on the Rating Label which is applied to your unit STORE DETAILS STORE NAME ADDRESS TELEPHON...

Страница 41: ...41 Attach your receipt to this page...

Страница 42: ...during the Warranty Period g Warranty Period means i where the Appliance is used for personal domestic or household use i e normal single family use as set out in the instruction manual the Appliance...

Страница 43: ...g from your purchase use or non use of the Appliance 10 For Appliances and services provided by Residentia Group in Australia the Appliances come with a guarantee by Residentia Group that cannot be ex...

Страница 44: ...This page is intentionally left blank Appliances Exactly what you need A RESIDENTIA GROUP INITIATIVE...

Отзывы: