PSI 10000 4U Serie
Group
Parameters & description
Analog interface Pin 14
Pin 14 of the analog interface (see section
) is by default assigned to only signal the
device alarm OVP. This parameter allows to also enable signaling the device alarms OCP
and OPP in 7 possible combinations:
•
Alarm OVP
= Signals only OVP
•
Alarm OCP
= Signals only OCP
•
Alarm OPP
= Signals only OPP
•
Alarm OVP+OCP
= Signals OVP or OCP
•
Alarm OVP+OPP
= Signals OVP or OPP
•
Alarm OCP+OPP
= Signals OCP or OPP
•
Alarm OVP+OCP+OPP
= Signals all three alarms
Pin 15
Pin 15 of the analog interface (see section
) is by default assigned to signal the regulation
mode CV. Alternatively, it allows to signal the DC output status:
•
Regulation mode
= Signals the CV regulation mode
•
DC status
= Signals the DC output status
DC output
State after power ON
Determines the condition of the DC output after power-up.
•
Off
= DC output is always off after switching on the device.
•
Restore
= Default, DC output state will be restored from last switch-off.
State after PF alarm
Determines the condition of the DC output after a power fail (PF) alarm:
•
Off
= Default, DC output remains off
•
Auto
= DC output will switch on again after the PF alarm cause is gone, if it has been
switched on before the alarm occurred
State after remote
Determines the condition of the DC output after leaving remote control either manually or by
command:
•
Off
= Default, DC output will always be off after leaving remote control
•
Auto
= DC output will keep the last state
State after OT alarm
Determines the condition of the DC output after an overtemperature (OT) alarm, once the
device has cooled down:
•
Off
= DC output will remain off
•
Auto
= Default, the device will automatically restore the situation before the OT alarm, which
usually means the DC output to be on