SAFETY

The unit is designed for indoor or outdoor use. 
WARNING – INSTALLATION AND SERVICE
•  The unit is only to be installed, operated, maintained and serviced by qualified 

persons only. Operation of units such as these can be hazardous and should be 
serviced by persons with the proper training and qualifications.

•  The unit and the Product Manual have markings, warning and instructions on the 

safe operation of the unit that must be adhered to.

•  The unit should be secured if necessary to prevent it from toppling over.
•  The unit is not to be used by the infirmed or children unless they are supervised 

by responsible persons qualified to carry out the supervision.

•  All panels must be re-installed after carrying out any maintenance work
WARNING – REFRIGERATION CIRCUIT
•  The chiller contains refrigerants under high pressure. The system also contains 

oils under high pressure. Before the refrigeration circuit can be opened, the 
refrigerant should be reclaimed to reduce pressure in the system

•  Failure to recover the refrigerant to relieve pressure or the use of refrigerants or 

refrigerant substitutes that are not specified for the unit may result in system 
rupture and explosion.

WARNING – WATER CIRCUIT
•  The liquids to be cooled must be compatible with the materials used in the 

constructions of this unit – the unit is designed to cool potable water only

•  Do not allow the unit to run dry
•  If the unit is connected to the mains supply and the water pressure is above 

500kPa a pressure limiting valve must be fitted

•  Minimum water temperature set point is 10C – do not set the water temperature 

below this

WARNING – MANUAL HANDLING
•  The units are quite heavy – the units should be handled by 2 people.
WARNING – ELECTRICAL
•  All wiring must be performed by qualified electricians. Improperly installed wiring 

and grounding may result in electrocution and fire hazards

•  The unit contains electrical components that operate at mains voltage and 

contains moving parts. It therefore must be isolated from the electrical supply 
before being serviced. All maintenance operations that require access to the 
unit must be carried out by suitably qualified technicians who have a thorough 
understanding of all necessary precautions associated with refrigeration and 
electrical machinery.

•  To avoid these hazards all wiring must be installed in accordance with all the local 

relevant safety standards for wiring

•  Where the above symbol is shown there are live electrical parts and the utmost 

care should be taken

•  Always isolate power from the unit when working on it.

 

 

 

 

Содержание ET14BL

Страница 1: ...T14CHILLER Tank Shower Chiller Unit ET14BMSLL BMS Alarm with Low Water Level ET14BL Backlit Sign ET14DL Downlight Call 1300 369 273 www enware com au Enware Australia Pty Limited 9 Endeavour Rd Caring...

Страница 2: ...losion WARNING WATER CIRCUIT The liquids to be cooled must be compatible with the materials used in the constructions of this unit the unit is designed to cool potable water only Do not allow the unit...

Страница 3: ...with the Tank Shower Alarm Junc on Box4 678657 Back to base signal Float sta on Sounder Shower switch Eyewash switch Act Light Maint Light Green Light Sign Back Light Interface1 Interface2 Interface3...

Страница 4: ...s filled with water again then proceed to connection of Back to Base signals and mains power supply to the junction box IMPORTANT TANK MUST BE FILLED WITH WATER AND COMMISSIONED BEFORE TURNING ON MAIN...

Страница 5: ...m B Connect the low water alarm signal cable to terminal marked c and d refer figure 1 excerpt from wiring diagram D2 TERMINAL DIODE D1 TERMINAL DIODE 11 12 21 22 24 24V 12 1 22 24 11 21 Sounder AB 24...

Страница 6: ...Main Power Input For The Junction Box Electrical Specification Voltage 230 VAC 10 6 50 Hz Maximum current 10A Connect main power supply A Wire the main power cable to L N E Earth terminals respective...

Страница 7: ...a Check the low water alarm signal can be active switch open when the tank is empty b Check there is no low water alarm signal switch closed when the tank is filled up with water NOTE The default trig...

Страница 8: ...eacon C ONNE C TOR 678666 U8 Amber B eacon C ONNE C TOR 678660 U5 Back Light2 C ONNE C TOR 678660 U4 Back Light1 Earth Moun ng material for cables 1 C able e mount Descrip on 151 28701 C able Tie Mou...

Страница 9: ...water level is lower than 1400L low water level switch of float station is opened Empty Water Alarm Function When Empty switch opened in float station identifies the tank is empty The back to base ma...

Страница 10: ...mute key switch is at off status and the shower eye wash is not activated ELECTRICAL SPECIFICATIONS BACK TO BASE ALARM INTERFACE Emergency Alarm Signal Style Normal closed switch Alarm switch open Vo...

Страница 11: ...shower pallet The chiller operation will be enabled by an external 24 VDC signal and connecting interface The chiller temperature sensing technology is connected to an external PT1000 temperature sens...

Страница 12: ...gnal Chiller enable signal The subsystem is controlled by an external 24 VDC signal to enable the operation of the chiller 0 VDC signal is to disable the chiller The 24VDC signal is controlled by syst...

Страница 13: ...ating Compressor starts at the same time as the fan do they both come on If not maybe faulty compressor or faulty fan Water not cold No flow through the heat exchanger check if there is frosting on th...

Страница 14: ...DRESS 9 Endeavour Rd Caringbah NSW 2229 Australia POSTAL ADDRESS P O Box 2545 Taren Point NSW 2229 Australia PHONE 61 2 8556 4000 1300 369 273 AUS WWW ENWARE COM AU INFO ENWARE COM AU ABN 23 003 988 3...

Отзывы: