enware ET14BL Скачать руководство пользователя страница 13

13 

Call 1300 369 273 

www.enware.com.au

SERVICE AND MAINTENANCE

Warning: Always isolate the power from the chiller before working on the unit.

Warning: Always ensure that personnel have read and understood the SAFETY section of this 
manual prior to working on the unit.

The units are designed to be low maintenance however some preventative maintenance is 
recommended to extend the life of the product.

Recommended preventative maintenance program:

Operational check

Frequency

Refrigerant Charge checked

Every 6 Months

Electrical connections are tight

Every 6 Months

Compressor amp draw

Every 12 Months

Pump amp draw

Every 12 Months

Condenser fins cleaned

Every 6 Months

Cables - inspect all cables to check no damage from hot spots or sharp points

Every visit

Troubleshooting:

Water not cold • If compressor does not start when controller reads >20C points to faulty controller

• If compressor does not start, check wiring integrity
• If compressor does not start, check temperature of the compressor – maybe over heating
• Compressor starts at the same time as the fan – do they both come on? If not, maybe faulty 
compressor or faulty fan

Water not cold • No flow through the heat exchanger – check if there is frosting on the evaporator – excess frosting 

points to low water flow
• No flow through the heat exchanger – remove one of the water lines and check flow
• Check current draw on the pump – maybe tight or tightening up

Water not cold • Problems with the refrigerant system – gas leaks will cause the unit to trip on the low-pressure safety 

switch installed next to the fan
• When the unit is running check the refrigerant flow though the sight glass – if there are bubbles then 
the system may need a top up of gas after a refrigeration mechanic has checked the system
• If it is suspected that there is a refrigerant leak do not run the unit – it my draw moisture into the 
system

Water leaks

• Check fittings – 4 in total by removing the access panel.
• Check that the pressure relief valve on the tank hasn’t opened – it is set at 1000kPa on the small 
units – 800kPa on the larger units - so there may be too much pressure which would point to the 
pressure limiting valve that is installed being faulty or the pressure relief valve being faulty

Содержание ET14BL

Страница 1: ...T14CHILLER Tank Shower Chiller Unit ET14BMSLL BMS Alarm with Low Water Level ET14BL Backlit Sign ET14DL Downlight Call 1300 369 273 www enware com au Enware Australia Pty Limited 9 Endeavour Rd Caring...

Страница 2: ...losion WARNING WATER CIRCUIT The liquids to be cooled must be compatible with the materials used in the constructions of this unit the unit is designed to cool potable water only Do not allow the unit...

Страница 3: ...with the Tank Shower Alarm Junc on Box4 678657 Back to base signal Float sta on Sounder Shower switch Eyewash switch Act Light Maint Light Green Light Sign Back Light Interface1 Interface2 Interface3...

Страница 4: ...s filled with water again then proceed to connection of Back to Base signals and mains power supply to the junction box IMPORTANT TANK MUST BE FILLED WITH WATER AND COMMISSIONED BEFORE TURNING ON MAIN...

Страница 5: ...m B Connect the low water alarm signal cable to terminal marked c and d refer figure 1 excerpt from wiring diagram D2 TERMINAL DIODE D1 TERMINAL DIODE 11 12 21 22 24 24V 12 1 22 24 11 21 Sounder AB 24...

Страница 6: ...Main Power Input For The Junction Box Electrical Specification Voltage 230 VAC 10 6 50 Hz Maximum current 10A Connect main power supply A Wire the main power cable to L N E Earth terminals respective...

Страница 7: ...a Check the low water alarm signal can be active switch open when the tank is empty b Check there is no low water alarm signal switch closed when the tank is filled up with water NOTE The default trig...

Страница 8: ...eacon C ONNE C TOR 678666 U8 Amber B eacon C ONNE C TOR 678660 U5 Back Light2 C ONNE C TOR 678660 U4 Back Light1 Earth Moun ng material for cables 1 C able e mount Descrip on 151 28701 C able Tie Mou...

Страница 9: ...water level is lower than 1400L low water level switch of float station is opened Empty Water Alarm Function When Empty switch opened in float station identifies the tank is empty The back to base ma...

Страница 10: ...mute key switch is at off status and the shower eye wash is not activated ELECTRICAL SPECIFICATIONS BACK TO BASE ALARM INTERFACE Emergency Alarm Signal Style Normal closed switch Alarm switch open Vo...

Страница 11: ...shower pallet The chiller operation will be enabled by an external 24 VDC signal and connecting interface The chiller temperature sensing technology is connected to an external PT1000 temperature sens...

Страница 12: ...gnal Chiller enable signal The subsystem is controlled by an external 24 VDC signal to enable the operation of the chiller 0 VDC signal is to disable the chiller The 24VDC signal is controlled by syst...

Страница 13: ...ating Compressor starts at the same time as the fan do they both come on If not maybe faulty compressor or faulty fan Water not cold No flow through the heat exchanger check if there is frosting on th...

Страница 14: ...DRESS 9 Endeavour Rd Caringbah NSW 2229 Australia POSTAL ADDRESS P O Box 2545 Taren Point NSW 2229 Australia PHONE 61 2 8556 4000 1300 369 273 AUS WWW ENWARE COM AU INFO ENWARE COM AU ABN 23 003 988 3...

Отзывы: