Constant Lights
Constant lights include the green light and back sign light.
• The green light is constantly on for 24/7
• The back sign light is constantly on for 24/7
Sounder Silencer
• The sounder is disabled if the mute key switch is at “off” status and the shower/eye wash is not
activated.
ELECTRICAL SPECIFICATIONS
BACK TO BASE ALARM INTERFACE
Emergency Alarm Signal
Style
Normal closed switch. Alarm = switch open.
Voltage
<= 48VDC
Current
<= 1A
Terminal Signature
‘A’, ‘B’
Cable diameter
5-10mm
Wire size
0.14 -1.5 mm²
Low Water Alarm Signal
Style
Normal closed switch. Alarm = switch open.
Voltage
<= 48VDC
Current
<= 1A
Terminal Signature
‘C’, ‘D’
Cable diameter
5-10mm
Wire size
0.14 -1.5 mm²