Note: Tank Shower frame is not Cyclone Rated when
mounted on FRP Grid Base.
Tank Shower frame with privacy panels is Category B Cyclone
Rated when bolted to the specified concrete slab and when
tank is at least half full of water.
MOUNTING ANCHORS
The frame is to be anchored to the reinforced concrete
footing specified below, using the 6 mounting plates on the
frame
(SEE FIGURE 1).
Each mounting plate has provision for 4 or 2 anchor bolts/rods
(NOT SUPPLIED), for a total of 20 to fully anchor the frame.
The 20 anchors must be of an M12 Stainless Steel Epoxy type
with 150mm embedment into the reinforced concrete footing
to meet Certification Requirements.
FOUNDATION: The footing is to be founded upon a minimum
150kPa material.
CONCRETE SPECIFICATIONS
ELEMENT SLUMP AGGREGATE
SIZE
CEMENT
TYPE
F’C - MPA
FOOTING
SLAB
80mm
20mm max.
GP
32
REINFORCED CONCRETE FOOTING SPECIFICATIONS
Reinforced concrete footing is to be a minimum
2000 x 2000 x 200mm
(SEE FIGURE 2)
with 16mm Diameter
Bars (with a Tensile Stress Capacity of 500 MPa) running at
200mm each way both top and bottom
(SEE FIGURE 3).
Footing must have a 50mm top and edge cover
and a 65mm bottom cover.
CONCRETE NOTES
1. All workmanship and materials shall be in accordance
with AS3600-2001 concrete structures code.
2. Concrete quality and clear concrete cover are to be as
specified.
3. Concrete element sizes do not include thickness of any
applied finishes.
4. All concrete shall be mechanically vibrated. The vibrator
shall not be used to spread concrete.
5. Reinforcement is shown diagramatically, not necessarily
shown in true projection.
6. All reinforcement shall be firmly supported on plastic
or MS plastic tipped or galvanised chairs placed at not
greater than 800mm centres both ways.
cyclone wind catergory B requirements
200
2000
2000
FIGURE 2
FIGURE 1
FIGURE 3
Cross Section showing reinforcement bars in one direction
200